
Section 2 — Installation
2-18
Part No. 750-363
2.9 MINIMUM BOILER OVERPRESSURE
To prevent the occurrence of flash steam within the boiler or system, hot water boilers must operate with
proper over-pressure. System over-pressure requirements are shown in
.
Note: The ASME Code Section IV limits the maximum setting of the excess temperature control to 250
F (121
C). This is to ensure
that water temperature will not reach the boiling point (steaming) and therefore, so as not to exceed the maximum limit of this
control and in compliance with the Code, the operating limit of 230
F (110
C) is set for normal boiler operation.
While proper overpressure is required, a means to relieve excess pressure at or beyond the design pressure of
the boiler must be provided. As boiler water is heated, expansion occurs. And this expansion must be
accounted for either with an expansion tank (air filled) or with a bladder type tank. These devices permit the
water pressure to expand outside of the boiler and not impact the pressure vessel or pressure relieving
device. In accordance with code, each boiler is equipped with an ASME approved safety relieving device
should pressure build-up occur.
Table 2-10: Model CFLC Minimum Over Pressure Requirements (100% water)
2.10 CONDENSATE REMOVAL AND TREATMENT
The condensate generated during normal boiler operation must be removed in accordance with local codes
and regulations. The condensate can be piped to a local treatment system or run into the optional
condensate treatment assembly.
The water trap must be filled with water prior to commissioning and checked or refilled at each required
maintenance interval.
Notice
The condensate occurring during operation in both the boiler and the flue gas pipeline should be neutralized and piped
to a safe drain. The conditions for the discharge of condensates into public drain systems are determined by the local
authorities and municipalities.
Condensate leaving the boiler normally has a pH of 4-6. The responsible authority will inform you if a higher
pH value is required for condensate piped to drain. The CFLC neutralization system contains a compound
which acts to increase the pH of the condensate flowing through it. The neutralization system comprises
the plastic neutralization tank with condensate inlet, granulate chamber and condensate outlet. The system
is installed per
Outlet Water Temperature
Minimum System Pressure
(°F)
(°C)
PSIG
Bar
130-180
54-82
12
0.83
181-185
83-85
15
1.03
186-205
86-96
18
1.24
206-215
97-101
24
1.66
216-225
102-107
30
2.07
226-240
108-116
42
2.90
Summary of Contents for ClearFire CFLC Series
Page 6: ...vi...
Page 14: ...Section 1 Introduction 1 8 Part No 750 363...
Page 16: ...Section 2 Installation 2 2 Part No 750 363...
Page 36: ...Section 2 Installation 2 22 Part No 750 363 Figure 2 13 Electrical Connections CFLC FALCON...
Page 38: ...Section 2 Installation 2 24 Part No 750 363...
Page 56: ...Section 3 Stack and Intake Vent Sizing and Installation 3 18 Part No 750 363...
Page 87: ...Section 6 Parts Part No 750 363 6 3 Figure 6 1 Boiler Mechanical Assembly CFLC 4000 5000...
Page 88: ...Section 6 Parts 6 4 Part No 750 363 Figure 6 2 Boiler Mechanical Assembly CFLC 6000 8000...
Page 95: ...Section 6 Parts Part No 750 363 6 11 Figure 6 10 Gas Train CFLC 6000 8000 optional 9 PPM NOx...
Page 97: ...Section 6 Parts Part No 750 363 6 13 Figure 6 12 Gas train CFLC 10000 12000 optional 9 PPM NOx...
Page 98: ...Section 6 Parts 6 14 Part No 750 363 Figure 6 13 Gas Train CFLC 4000 5000 Propane...
Page 99: ...Section 6 Parts Part No 750 363 6 15 Figure 6 14 Gas Train CFLC 6000 8000 Propane...
Page 100: ...Section 6 Parts 6 16 Part No 750 363 Figure 6 15 Gas Train CFLC 10000 12000 Propane...
Page 105: ...Section 6 Parts Part No 750 363 6 21 Figure 6 20 Control Panel...
Page 106: ...Section 6 Parts 6 22 Part No 750 363 Figure 6 21 Cables and Cable Harness...
Page 108: ...Section 6 Parts 6 24 Part No 750 363 Figure 6 23 Casing Insulation 4000 5000 cont d...
Page 109: ...Section 6 Parts Part No 750 363 6 25 Figure 6 24 Casing Insulation 6000 8000...
Page 110: ...Section 6 Parts 6 26 Part No 750 363 Figure 6 25 Casing Insulation 6000 8000 cont d...
Page 115: ...APPENDIX A Falcon Parameters...
Page 116: ......
Page 124: ......
Page 144: ......
Page 145: ...APPENDIX C Gas Valve Page C 3 Siemens Gas Valve Page C 25 Dungs Gas Valve CFLC 4000 5000...
Page 146: ......
Page 147: ...Appendix C Gas Valve C 3...
Page 148: ...Gas Valve Appendix C C 4...
Page 149: ...Appendix C Gas Valve C 5...
Page 150: ...Gas Valve Appendix C C 6...
Page 151: ...Appendix C Gas Valve C 7...
Page 152: ...Gas Valve Appendix C C 8...
Page 153: ...Appendix C Gas Valve C 9...
Page 154: ...Gas Valve Appendix C C 10...
Page 155: ...Appendix C Gas Valve C 11...
Page 156: ...Gas Valve Appendix C C 12...
Page 157: ...Appendix C Gas Valve C 13...
Page 158: ...Gas Valve Appendix C C 14...
Page 159: ...Appendix C Gas Valve C 15...
Page 160: ...Gas Valve Appendix C C 16...
Page 161: ...Appendix C Gas Valve C 17...
Page 162: ...Gas Valve Appendix C C 18...
Page 163: ...Appendix C Gas Valve C 19...
Page 164: ...Gas Valve Appendix C C 20...
Page 165: ...Appendix C Gas Valve C 21...
Page 166: ...Gas Valve Appendix C C 22...
Page 167: ...Appendix C Gas Valve C 23...
Page 168: ...Appendix C Gas Valve C 24...
Page 186: ...Appendix C Gas Valve C 42...
Page 187: ...APPENDIX D Falcon Alert Hold and Lockout Codes...
Page 188: ......
Page 208: ......
Page 210: ......
Page 231: ...Appendix E Falcon Lead Lag E 23 Figure 11 Falcon LL with EMS for remote enable remote setpoint...
Page 232: ...Falcon Lead Lag Appendix E E 24 Figure 12 Falcon Lead Lag with EMS for remote comms monitoring...
Page 245: ...Appendix E Falcon Lead Lag E 37 Model CFW ClearFire hydronic boiler...
Page 282: ......
Page 283: ...APPENDIX F Falcon Program Module...
Page 284: ......
Page 285: ...Appendix F Program Module F 3...
Page 286: ...Program Module Appendix F F 4...
Page 287: ...Appendix F Program Module F 5...
Page 288: ...Program Module Appendix F F 6...
Page 289: ......
Page 290: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...