Falcon Lead Lag
Appendix E
E-14
Modulation backup sensor
(hot water) - this parameter determines the setpoint source (‘backup
sensor’) in the event of a header temperature sensor failure. If
Disable
is selected then no backup
will be used. If
Lead Outlet
is selected then the outlet temperature of the lead boiler will be used
as the backup during firing. If
Slave Outlet Average
is selected then average of the outlet
temperatures of all slave boilers that are firing will be used as a backup.
Table 2b - Lead Lag Master Configuration Parameters - Advanced Settings, Steam
Parameter
Range
CB Default Setting
Installation Setting
Modulation Parameters
Modulation sensor
S1 (J8-4) Steam Sensor
S2 (J8-6) Steam Sensor
S2 (J8-6) Steam Sensor
Off hysteresis
psi
5
On hysteresis
psi
0
Hysteresis step time
hr min sec
0 sec
P gain
0-400
10
I gain
0-400
25
D gain
0-400
0
Steam Parameters
Demand switch
Stat Terminal
Mod Sensor
Disabled
Stat Terminal
Setpoint source
Local
Local
4-20mA -
Not compatible with Falcon steam lead lag.
Setpoint
0-135 psi
10
Time of day setpoint
0-135 psi
0
Algorithms Parameters
Lead selection method
Sequence order
Measured run time
Sequence order
Lag selection method
Sequence order
Measured run time
Sequence order
Lead rotation time
day hr min
120 hrs
Force lead rotation time
day hr min
168 hrs
Rate Allocation Parameters
Base load common
0-100%
75%
Add Stage Parameters
Add stage method
Error threshold
Firing rate threshold
Disabled
Firing rate threshold
Add stage detection time
hr min sec
3 min
Error threshold
0 deg F to 234 deg F (-17 deg C
to 112 deg C)
5 deg F
Rate offset
E%
0%
Add Stage interstage delay
hr min sec
10 min
Drop Stage Parameters
Drop stage method
Error threshold
Firing rate threshold
Firing rate threshold
Drop stage detection time
hr min sec
2 min
Error threshold
psi
3 psi
Rate offset
E%
-3%
Interstage delay
hr min sec
5 min
Summary of Contents for ClearFire CFLC Series
Page 6: ...vi...
Page 14: ...Section 1 Introduction 1 8 Part No 750 363...
Page 16: ...Section 2 Installation 2 2 Part No 750 363...
Page 36: ...Section 2 Installation 2 22 Part No 750 363 Figure 2 13 Electrical Connections CFLC FALCON...
Page 38: ...Section 2 Installation 2 24 Part No 750 363...
Page 56: ...Section 3 Stack and Intake Vent Sizing and Installation 3 18 Part No 750 363...
Page 87: ...Section 6 Parts Part No 750 363 6 3 Figure 6 1 Boiler Mechanical Assembly CFLC 4000 5000...
Page 88: ...Section 6 Parts 6 4 Part No 750 363 Figure 6 2 Boiler Mechanical Assembly CFLC 6000 8000...
Page 95: ...Section 6 Parts Part No 750 363 6 11 Figure 6 10 Gas Train CFLC 6000 8000 optional 9 PPM NOx...
Page 97: ...Section 6 Parts Part No 750 363 6 13 Figure 6 12 Gas train CFLC 10000 12000 optional 9 PPM NOx...
Page 98: ...Section 6 Parts 6 14 Part No 750 363 Figure 6 13 Gas Train CFLC 4000 5000 Propane...
Page 99: ...Section 6 Parts Part No 750 363 6 15 Figure 6 14 Gas Train CFLC 6000 8000 Propane...
Page 100: ...Section 6 Parts 6 16 Part No 750 363 Figure 6 15 Gas Train CFLC 10000 12000 Propane...
Page 105: ...Section 6 Parts Part No 750 363 6 21 Figure 6 20 Control Panel...
Page 106: ...Section 6 Parts 6 22 Part No 750 363 Figure 6 21 Cables and Cable Harness...
Page 108: ...Section 6 Parts 6 24 Part No 750 363 Figure 6 23 Casing Insulation 4000 5000 cont d...
Page 109: ...Section 6 Parts Part No 750 363 6 25 Figure 6 24 Casing Insulation 6000 8000...
Page 110: ...Section 6 Parts 6 26 Part No 750 363 Figure 6 25 Casing Insulation 6000 8000 cont d...
Page 115: ...APPENDIX A Falcon Parameters...
Page 116: ......
Page 124: ......
Page 144: ......
Page 145: ...APPENDIX C Gas Valve Page C 3 Siemens Gas Valve Page C 25 Dungs Gas Valve CFLC 4000 5000...
Page 146: ......
Page 147: ...Appendix C Gas Valve C 3...
Page 148: ...Gas Valve Appendix C C 4...
Page 149: ...Appendix C Gas Valve C 5...
Page 150: ...Gas Valve Appendix C C 6...
Page 151: ...Appendix C Gas Valve C 7...
Page 152: ...Gas Valve Appendix C C 8...
Page 153: ...Appendix C Gas Valve C 9...
Page 154: ...Gas Valve Appendix C C 10...
Page 155: ...Appendix C Gas Valve C 11...
Page 156: ...Gas Valve Appendix C C 12...
Page 157: ...Appendix C Gas Valve C 13...
Page 158: ...Gas Valve Appendix C C 14...
Page 159: ...Appendix C Gas Valve C 15...
Page 160: ...Gas Valve Appendix C C 16...
Page 161: ...Appendix C Gas Valve C 17...
Page 162: ...Gas Valve Appendix C C 18...
Page 163: ...Appendix C Gas Valve C 19...
Page 164: ...Gas Valve Appendix C C 20...
Page 165: ...Appendix C Gas Valve C 21...
Page 166: ...Gas Valve Appendix C C 22...
Page 167: ...Appendix C Gas Valve C 23...
Page 168: ...Appendix C Gas Valve C 24...
Page 186: ...Appendix C Gas Valve C 42...
Page 187: ...APPENDIX D Falcon Alert Hold and Lockout Codes...
Page 188: ......
Page 208: ......
Page 210: ......
Page 231: ...Appendix E Falcon Lead Lag E 23 Figure 11 Falcon LL with EMS for remote enable remote setpoint...
Page 232: ...Falcon Lead Lag Appendix E E 24 Figure 12 Falcon Lead Lag with EMS for remote comms monitoring...
Page 245: ...Appendix E Falcon Lead Lag E 37 Model CFW ClearFire hydronic boiler...
Page 282: ......
Page 283: ...APPENDIX F Falcon Program Module...
Page 284: ......
Page 285: ...Appendix F Program Module F 3...
Page 286: ...Program Module Appendix F F 4...
Page 287: ...Appendix F Program Module F 5...
Page 288: ...Program Module Appendix F F 6...
Page 289: ......
Page 290: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...