Operator's Manual: Models CB-1500 & CB-2500 (230 V / 50 Hz)
8-6
Installing the Make-up Air Louver
All louvers and grills, regardless of the material from which they are made, must be FIXED in the OPEN
position OR be interlocked with the appliance so that they will open automatically during the operation of the
appliance. The interlock must be placed on the driven member.
NOTE:
It is very important to follow these instructions carefully to ensure proper performance of the louver.
1.
The louver must not be close to the furnace. The fresh air should travel at least 10-13m
(40-50 feet) before reaching the furnace so the air warms up. The furnace will not heat well if it
is receiving cold return air.
2.
The louver must be high in the sidewall of the building so the cold fresh air does not blow across
the floor level and chill the service personnel.
3.
The louver should be installed in the opposite wall from the location of the exhaust fan. This
will quickly vent diesel exhaust from the top of the building and reduce the amount of run time
for the exhaust fan.
CALCULATED OPENING SIZE
cm
2
in
2
REQUIRED LOUVER / GRILL SIZE
cm in
0 – 528 0 – 82
25 x 25 10 x 10
529 – 836 83 – 130
30 x 30 12 x 12
837 – 1,445 131 – 224 41 x 41 16 x 16
1,446 – 1,923 225 – 299
46 x 46 18 x 18
1,924 – 2,390 300 – 370
51 x 51 20 x 20
2,391 – 3,166 371 – 490
61 x 61 24 x 24
3,167 – 4,769 491 – 739
76 x 76 30 x 30
4,770 – 7,150 740 – 1109
91 x 91 36 x 36
7,151 – 9,182 1,110 – 1,424 107 x 107 42 x 42
9,183 – 12,355 1,425 – 1,915 122 x 122 48 x 48
12,356 – 15,499 1,916 – 2,400 137 x 137 54 x 54
15,500 – 19,650 2,401 – 3,045 152 x 152 60 x 60
Installing a Make-up Air Louver (continued)
Summary of Contents for CB-500 series
Page 2: ......
Page 4: ......
Page 18: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 1 10 ...
Page 60: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 4 26 ...
Page 66: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 5 6 ...
Page 74: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 7 4 ...
Page 96: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 10 8 ...
Page 114: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz A 18 ...
Page 122: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz D 2 ...