4-8
Oil Tank Installation Specifications
Ensure that your tank installation adheres to the
following safety guidelines as stated here and in
Section 1
of this manual.
The tank safety label (shown at right) also
summarizes these important specifications for tank
installation and usage. If you do not have a copy of
this label, please contact your Clean Burn dealer for
a copy, which is to be affixed directly to your used
oil supply tank.
•
The tank installation must meet all
national and local codes.
Consult your
local municipal authorities for more
information as necessary.
•
Use a minimum
1000 Liter tank
. DO NOT
use drums as a substitute for an appropriate
tank. The tank must be large enough to allow
water, sludge, etc. to settle out of the used oil.
•
Single wall tanks must have a
shut-off
valve
on the side of the tank to allow
the water, sludge, etc. to be drained from
the bottom of the tank.
•
All
unused openings in the tank must be
plugged
or capped off.
•
For optimal system functioning, Clean Burn
Recommends inside tank installations as
shown in Figures 4A, 4B, and 4J.
•
The tank must be
vented to the outside
of
the building using iron or steel pipe and
fittings with an approved vent cap.
•
Carefully review the oil tank and pump
installation details as shown in Figures 4A,
4B, 4F, and 4J including the metering pump
installation and specifications for the oil
line installation. (Procedures for installing
these components can be found in the
following pages.)
•
Ensure that the oil supply tank is
properly
maintained
; refer to Section 9 in this manual
for related procedures.
ATTENTION: For outside tank installations and/or tanks larger than 1890 Liters (500 gallons)
,
contact the local Clean Burn distributor for installation recommendations and specifications.
Summary of Contents for CB-500 series
Page 2: ......
Page 4: ......
Page 18: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 1 10 ...
Page 60: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 4 26 ...
Page 66: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 5 6 ...
Page 74: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 7 4 ...
Page 96: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 10 8 ...
Page 114: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz A 18 ...
Page 122: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz D 2 ...