Operator's Manual: Models CB-1500 & CB-2500 (230 V / 50 Hz)
4-21
Figure 4M - CB-1500 Installation of "Class A" Stack Through Sidewall
(CB-2500 is similar)
Installing the Stack (continued)
I88897−A
3 m
(10’)
MINIMUM
VERTICA
L STAC
K HEIG
HTPLUS 3
0 cm (
1’)
F
O
R E
VER
Y FI
TTIN
G
TO
MA
INTAIN PRO
PER DRAFT OVERFIRE
3 m (10’)
"CLASS A" STACK CAP − NON−RESTRICTIVE TYPE
TO ALLOW FREE FLOW OF THE STACK GASES
FURNACE OPERATION.
IS ESSENTIAL FOR PROPER
BAROMETRIC DAMPER
−0.02 W.C. DRAFT OVERFIRE
SEE SECTION 8
"CLA
SS A"
STACK
COMPO
NENTS
INSUL
A
TED S
TACK WI
TH A STA
INLESS
STEEL
LINER
"CLASS A" STACK
PENETRATION AND
CLEAN−OUT TEE
SINGLE WALL STACK
MIN. 24 GAUGE
60
cm
(
2’
)
S
E
S
L
E
R
O
M
WARNING! ENSURE PROPER
CLEARANCES BETWEEN STACK
COMPONENTS AND COMBUSTIBLES
PER ALL APPLICABLE CODES.
DRAFT AT BREECH
SETTING DRAFT.
ADJUST BAROMETRIC
6 mm (1/4") HOLE FOR
DAMPER FOR −.04 W.C.
STACK SIZE:
MIN. 20 cm (8")
WARNING!
MAKE SURE TO INSTALL
THE PROPER WALL SUPPORT SYSTEM
TO SAFELY SUPPORT THE STACK
NOTE: THE LAST STACK SECTION SHALL EXTEND AT LEAST
90 cm (3’) ABOVE THE HIGHEST POINT AT WHICH IT COMES IN
CONTACT WITH THE ROOF AND AT LEAST 60 cm (2’) HIGHER
THAN ANY RIDGE, PARAPET, WALL OR ROOF STRUCTURE
WITHIN 3 m (10’) OF IT.
CONNECTOR BLOCK
AIR OIL
Nr . 057 H7 036
T yp e BHO 6 4
D anfoss
220 -240V 50-60 Hz 3W
ts 10s
Summary of Contents for CB-500 series
Page 2: ......
Page 4: ......
Page 18: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 1 10 ...
Page 60: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 4 26 ...
Page 66: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 5 6 ...
Page 74: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 7 4 ...
Page 96: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz 10 8 ...
Page 114: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz A 18 ...
Page 122: ...Operator s Manual Models CB 1500 CB 2500 230 V 50 Hz D 2 ...