(4)
This is the minimum recommended cable cross sectional area for the maximum AC input current (see data-
sheet) using multi-core copper cables with three loaded conductors for installations in conduit in a thermally
insulated wall (A2 method according to IEC-60364-5-52).
The final cross section might be different if the installation method is another one, at any case, it has to be
calculated by the installer, taking into account the cable materials, the conditions of installation and distances.
(5)
This is the maximum cable cross sectional area accepted by the Main circuit breaker.
Raption 50 - 400V Models
MODELS
CCS1
CCS2
CCS1 CHA
CCS2 CHA
CCS1 T1C32
CCS2 T2C32
CCS1 T2S32
CCS2 T2S32
CCS1-CHA T1C32
CCS2-CHA T2C32
CCS1-CHA T2S32
CCS2-CHA T2S32
CCS2-CHA T2C63
Minimum recommended
cable cross sectional area
(4)
25 mm
2
50 mm
2
50 mm
2
70 mm
2
Maximum cable cross
sectional area
(5)
95 mm
2
95 mm
2
95 mm
2
95 mm
2
35
Installation Guide