(8)
This is the minimum recommended cable cross sectional area for the maximum AC input current (see data-
sheet) using multi-core copper cables with three loaded conductors for installations in conduit in a thermally
insulated wall (A2 method according to IEC-60364-5-52).
The final cross section might be different if the installation method is another one, in any case, it has to be
calculated by the installer, taking into account the cable materials, the conditions of installation and distances.
(9)
This is the maximum cable cross sectional area accepted by the Main circuit breaker.
4-
Use a phillip screwdriver in order to connect the electric terminals. The maximum tightening
torque has to be 5 Nm.
5-
Follow the label under the circuit breaker, connect the cables to the left and right terminal,
the terminals of the middle must be free.
In case of 480V power supply, Install a step-down transformer from the 480 V to 220 V mains
with a power of 10 kVA, to guarantee the correct operation of the Charge Point.
Raption 50 / Raption 50 HV / Raption 50 EVO - 480V Models
MODELS
Input
CCS1
CCS1 CHA
CCS1 T1C32
CCS1 T2S32
CCS1-CHA T1C32
CCS1-CHA T2S32
Minimum recom-
mended cable cross
sectional area
(8)
Three-phase 480 V
25 mm
2
25 mm
2
25 mm
2
Single-phase 208 - 240 V
-
10 mm
2
10 mm
2
Maximum cable
cross sectional
area
(9)
Three-phase 480 V
95 mm
2
95 mm
2
95 mm
2
Single-phase 208 - 240 V
95 mm
2
95 mm
2
95 mm
2
Raption 100 - 480V Models
MODELS
Input
CCS1
CCS1 CHA
CCS1 T1C32
CCS1 T2S32
CCS1-CHA T1C32
CCS1-CHA T2S32
Minimum recom-
mended cable cross
sectional area
(8)
Three-phase 480 V
70 mm
2
70 mm
2
70 mm
2
Single-phase 208 - 240 V
-
10 mm
2
10 mm
2
Maximum cable cross
sectional area
(9)
Three-phase 480 V
150 mm
2
150 mm
2
150 mm
2
Single-phase 208 - 240 V
150 mm
2
150 mm
2
150 mm
2
39
Installation Guide
Raption
Summary of Contents for Raption 100
Page 1: ...Raption Series INSTALLATION GUIDE M186A01 03 21D...
Page 2: ...2 Raption Installation Guide...
Page 15: ...15 Installation Guide Raption...
Page 16: ...3 A Dimensions Units specified in millimeters 16 Raption Installation Guide...
Page 56: ...56 Raption Installation Guide...
Page 58: ...58 Raption Installation Guide...
Page 59: ...59 Installation Guide Raption...