UNIT INfORMATION
Address 1
(1)
Address 2
(2)
Name
Description
Unit
7078-7079
7539
Fl_min
Minimum value of φ
º
7080-7081
7540
Fl_max
Maximum value of φ
º
7082-7083
7541
FrEq_min
Minimum frequency value
Hz
7084-7085
7542
FrEq_max
Maximum value of frequency
Hz
7086-7087
7543
PAv_min
Minimum value of average active power
W
7088-7089
7544
PAv_max
Maximum value of average active power
W
7090-7091
7545
UAv_min
Minimum value of average voltage
V
7092-7093
7546
UAv_max
Maximum value of average voltage
V
7094-7095
7547
FAv_min
Minimum value of average frequency
Hz
7096-7097
7548
FAv_max
Maximum value of average frequency
Hz
7098-7099
7549
EP_PoS1
Active energy generated
(3)
100 MWh
7100-7101
7550
EP_PoS2
Active energy generated (module 100000.0)
kWh
7102-7103
7551
EP_nEG1
Active energy consumed
(3)
100 MWh
7104-7105
7552
EP_nEG2
Active energy consumed (module 100000.0)
kWh
7106-7107
7553
Eq_PoS1
Reactive energy generated
(3)
100
Mvarh
7108-7109
7554
Eq_PoS2
Reactive energy generated (module 100000.0)
kvarh
7110-7111
7555
Eq_nEG1
Reactive energy consumed
(3)
100
Mvarh
7112-7113
7556
Eq_nEG2
Reactive energy consumed (module 100000.0)
kvarh
(1)
Value in two consecutive 16-bit records.
(2)
Value in one 32-bit record.
(3)
The energy meter records 7550, 7552, 7554 and 7556 reset to zero when the value
9999999.9 K is exceeded
61
Instruction Manual
DHB-302 DHB-324
Summary of Contents for DHB-302
Page 1: ...INSTRUCTION MANUAL M044B01 03 17A Single phase Vac analyzer DHB 302 DHB 324...
Page 2: ...2 DHB 302 DHB 324 Instruction Manual...
Page 64: ...Figure 60 Dimensions of the DHB 3xx 64 DHB 302 DHB 324 Instruction Manual...
Page 66: ...8 CE CERTIFICATE 66 DHB 302 DHB 324 Instruction Manual...