The options are:
n-on
n-off
on
off
Manual activation of the
alarm relay.
Manual deactivation of
the alarm relay.
To move from one option to another, press the
button repeatedly.
When you see the option you want, validate by pressing the
button.
The unit goes back to the screen shown in
.
To move to the next parameter on the menu, press the
button.
Default value
: n-on.
4�6�3�6� CONNeCTION AND DISCONNeCTION DeLAy
This screen is used to configure the connection and disconnection delay for the alarm.
The screen flashes between the symbol and the configured value (
).
figure 36:Connection/disconnection delay screens�
To edit the parameter, press the
button.
To modify the value of the selected digit, press the
button repeatedly.
To jump to the next digit, press the
button
Once at the desired value, validate by pressing the
button. The unit goes back to the
screen shown in
To move to the next parameter on the menu, press the
button.
Range
: 0 ... 900 seconds.
Default value:
0
33
Instruction Manual
DHB-302 DHB-324