DISpLAy
Address
Symbol
Description
4012
CoLUp
Upper colour
Value
Description
0
red
1
green
2
orange
Address 1
(1)
Address 2
(2)
CoLLo
Lower colour change limit.
-19999 M ... 99999 M
7200-7201
7600
Address 1
(1)
Address 2
(2)
CoLx1
Upper colour change limit.
-19999 M ... 99999 M
7202-7203
7601
Address 1
(1)
Address 2
(2)
ovrLo
Underflow.
-19999 M ... 99999 M
7204-7205
7602
Address 1
(1)
Address 2
(2)
ovrX!
Overflow.
-19999 M ... 99999 M
7206-7207
7603
(1)
Value in two consecutive 16-bit records.
(2)
Value in one 32-bit record.
4.7.3.3- Configuration: Alarm parameters.
The Modbus address is in decimal format.
The read and write functions are enabled for all of these variables.
Table 10:Modbus memory map (Table 3)�
ALARMS
Address
Symbol
Description
4013
P.a1
Parameter (Alarm 1)
Value
Description
0
RMS voltage
1
RMS current
2
Active power
3
Reactive power
4
Apparent power
5
Power factor (cos φ)
6
tg φ
7
φ
8
Frequency
9
Active energy generated
10
Active energy Consumed
11
Reactive energy generated
12
Reactive energy consumed
13
Maximum demand for active power
14
Average voltage (10 minutes)
15
Average frequency (10 minutes)
52
DHB-302 DHB-324
Instruction Manual
Summary of Contents for DHB-302
Page 1: ...INSTRUCTION MANUAL M044B01 03 17A Single phase Vac analyzer DHB 302 DHB 324...
Page 2: ...2 DHB 302 DHB 324 Instruction Manual...
Page 64: ...Figure 60 Dimensions of the DHB 3xx 64 DHB 302 DHB 324 Instruction Manual...
Page 66: ...8 CE CERTIFICATE 66 DHB 302 DHB 324 Instruction Manual...