4.7.3.4- Configuration: Output menu parameters (DHB-324 model).
The Modbus address is in decimal format.
The read and write functions are enabled for all of these variables.
Table 11:Modbus memory map (Table 4)�
OUTpUTS (DHB-324)
Address
Symbol
Description
4029
p.an
Analogue output parameter
Value
Description
0
RMS voltage
1
RMS current
2
Active power
3
Reactive power
4
Apparent power
5
Power factor (cos φ)
6
tg φ
7
φ
8
Frequency
9
Active energy generated
10
Active energy Consumed
11
Reactive energy generated
12
Reactive energy consumed
13
Maximum demand for active power
14
Average voltage (10 minutes)
15
Average frequency (10 minutes)
4030
typa
Type of analogue output
Value
Description
0
Voltage output 0...10 V
1
Current output 0...20 mA
2
Current output 4...20 mA
4031
bauds
Modbus Communications: baud rate
Value
Description
0
4800 bauds
1
9600 bauds
2
19200 bauds
3
38400 bauds
4032
prot
Modbus Communications: Transmission protocol
Value
Description
0
8 data bits - no parity - 2 stop bits
1
8 data bits - even parity - 1 stop bit
2
8 data bits - odd parity - 1 stop bit
3
8 data bits - no parity - 1 stop bit
4033
addr
Modbus address.
0 ... 247
4034
save
Apply the changes entered in the RS-485 interface
Value
Description
0
Do not save changes
1
Save changes
56
DHB-302 DHB-324
Instruction Manual