82
AFQm
Instruction Manual
The points to be inspected are:
1�-
Set the
AFQm
in STOP mode and open the main switch (
OFF
position).
2�-
Wait 1 minute for the capacitors to discharge.
3�-
Clean the ventilation grilles, removing the dust.
4�-
Check the status and torque of the electrical connections, as well as the mechanical attach-
ment to the wall.
5�-
Reset the standard maintenance meter, to do so:
Access the main setup screen.
Figure 79:
Main configuration screen.
Press the
Edit key and enter the password used to access the maintenance screen
(
Maintenance password:
8888
).
The screen shown in
Figure 80
will be displayed.
Figure 80: Maintenance screen�
Press the
key to reset the maintenance meter.
Summary of Contents for AFQm Series
Page 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 19B...
Page 2: ...2 AFQm Instruction Manual...
Page 103: ...103 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 98 Dimensions Cabinet type AFQm...
Page 105: ...105 Instruction Manual AFQm 14 CE CERTIFICATE...
Page 106: ...106 AFQm Instruction Manual...
Page 107: ...107 Instruction Manual AFQm...