35
Instruction Manual
AFQm
3�8�2�- CONNECTING CABINETS
Note:
The
200A
(
AFQm-xxx-200C
),
300A
(
AFQm-xxx-300C
) and
400A
(
AFQm-xxx-400C
)
cabinets are made up of 2, 3 and 4
100A
devices in parallel. Both the parallel configuration and
connection are factory-set.
To connect multiple cabinets in parallel, follow these steps:
1�-
Select the cabinet that is to contain the “
master
” device.
2.-
Connect the “
master
” cabinet. The current transformers are only connected to the “
master
”
cabinet.
3.-
Connect the “
slave
” cabinets.
4�-
Connect all of the devices using the communication cables (
Table 14
).
Connect the
OUT
terminal from the
final slave device in the “
master
” cabinet to the
IN
terminal
from the “
master
” device of the following cabinet, and the
OUT
terminal from the final “
slave”
device in this cabinet to the
IN
terminal of the “
master
” device of the following cabinet, and so
on (
Figure 29
).
Master
Slave
Slave
(*)
Connections already included in the cabinets
IN
OUT
2
3
2
3
IN
OUT
2
3
2
3
OUT
IN
2
3
IN
2
3
OUT
2
3
2
3
AFQm-xxx-200C
(*)
(*)
OUT
IN
2
3
IN
2
3
OUT
2
3
2
3
(*)
ON
R
BUS
ON
R
BUS
ON
R
BUS
ON
R
BUS
ON
R
BUS
ON
R
BUS
Figure 29:Connecting 3 devices in parallel, using the communication cable (200 A Master AFQm)�
5�-
Configure the installation in the “
master
” device (see
“7.- CONFIGURATION”
).
6�-
Complete the configuration of the slave devices
(see
“7.- CONFIGURATION”
).
7.-
Enable the terminator switch for parallel connection,
R
BUS
(Terminal No 2 of
Table 12
) in the
bus end devices only. Then disable in the other devices.
Summary of Contents for AFQm Series
Page 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 19B...
Page 2: ...2 AFQm Instruction Manual...
Page 103: ...103 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 98 Dimensions Cabinet type AFQm...
Page 105: ...105 Instruction Manual AFQm 14 CE CERTIFICATE...
Page 106: ...106 AFQm Instruction Manual...
Page 107: ...107 Instruction Manual AFQm...