Figure 32:
Current in the load, in the filter and in the mains.
4.3.- RATED CURRENT DIMENSIONS
The purchased active filter must be sized for the harmonic currents it has to filter. The rated
current of the
AFQm
must be at least 20% higher than the maximum level of harmonics to be
filtered. This factor may be higher depending on the installation features.
The active filters can suffer from overloading when trying to cancel the harmonic currents in
high-impedance, short-circuit mains. The clearest symptom for detecting such cases is that
they originally start from a
THD(V)
(under voltage) of over 3%. It has been seen that the higher
the initial
THD(V)
, the greater the chance of filter overload.
The reason for this behaviour is that the load does not behave as a current source, but rather
the larger the harmonic current absorbed by the filter the more harmonics are produced by the
load, which can produce up to more than double what was initially measured.
To avoid this phenomenon, it is best to oversize the active filter by multiplying the initial current
of harmonics measured in the load by a
safety factor
(
FS
h
). In other words:
I
FILTER
(AFQm) = [FS
h
* I
LOAD
* THD(I)]
Where:
I
FILTER
(AFQm)
: rated current of the active filter.
FS
h
: safety factor > 1.2.
I
LOAD
: maximum current of the load.
THD(I)
: harmonic distortion of the load current.
Equation 5:Rated current of the AFQm�
Summary of Contents for AFQm Series
Page 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 19B...
Page 2: ...2 AFQm Instruction Manual...
Page 103: ...103 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 98 Dimensions Cabinet type AFQm...
Page 105: ...105 Instruction Manual AFQm 14 CE CERTIFICATE...
Page 106: ...106 AFQm Instruction Manual...
Page 107: ...107 Instruction Manual AFQm...