7. Turn on power at the source breaker.
When the disinfecting modules are inserted in the receiver box and power is on at the source,
the modules are automatically powered on and start flashing red indicating the modules are
not connected to a network.
8. In the CounterAct application:
a) Log into the CounterAct application (on page 23).
b) Create a room (on page 40).
c) Add the fixtures to the room (on page 40).
d) Register the fixtures (on page 42).
e) Configure the scheduler (on page 43) to determine when you want disinfection to occur.
9. When all the fixtures are installed, configured, and turned on, run the fixtures in Disinfection
mode and using a meter, verify the optical power output (on page 43) are below the ACGIH
Risk Group Exempt levels for the space.
When Disinfection mode is not on, the fixture is in Standby mode (LED indicator ring is solid
greed unless configured for Stealth mode).
Planning the layout and power of the site
Planning the site can help determine the installation position and power to help facilitate pairing and
configuration work.
Christie strongly recommends planning out the site before arriving at the site for installation.
1. Select the appropriate ceiling and wall finishes.
UV and optical radiation can be reflected by surrounding surfaces such as ceilings and walls. As
the reflective properties of surfaces can vary widely, follow the manufacturer’s
recommendations for selecting appropriate ceiling and wall finishes.
2. Make a plan of the installation position for each fixture.
For example, the site plan should show the planned location of all the fixtures.
3. Make a plan for the power to be used at the site.
Planning the installation height
Plan the installation height for CounterAct.
The mode lamp mode the fixture will be run in depends on the installation height:
•
Installed in a ceiling with a minimum height of 6.7 m (22 feet) to 8.5 m (28 feet)—Single-lamp
mode
•
Installed in a ceiling with a minimum height of 8.5 m (28 feet)—Dual-lamp mode
Below 6.7 m (22 feet) this model of the fixture should not be used. Contact Christie Sales for options
suitable for installation in ceilings below 6.7 m (22 feet).
Installation and setup
CounterAct Installation and Setup Guide
21
020-103456-02 Rev. 1 (12-2021)