9.7 2-Color Zero Adjustment (*IR-HAQ)
Performs 2-color adjustment.
Collimate the thermometer and sight the black body furnace to
input the temperature of the furnace.
1) From zero/span adjustment mode display, push
SEL
key several
times to display "2C Z" on the sub display.
2) Push
key or
key to change numeric value.
3) Blinking stops by pushing
ENT
key and the blinking digit moves
its position from lower place to the higher place and the
registration is completed.
9.8 2-Color Span Adjustment (*IR-HAQ)
Performs 2-color adjustment.
Collimate the thermometer and sight the black body furnace to
input the temperature of the furnace.
1) From zero/span adjustment mode display, push
SEL
key several
times to display "2C S" on the sub display.
2) Push
key or
key to change numeric value.
3) Blinking stops by pushing
ENT
key and the blinking digit moves
its position from lower place to the higher place and the
registration is completed.
Remark
Remark
Caution
Caution
At setting, if zero adjustment value (input temperature or measured temperature) exceeds span
adjustment value (input temperature or measured temperature), setting becomes disabled and
displays 'Er6'.
・
Setting range is 0 to 9999.
・
Setting of factory default is 600.
At setting, if span adjustment value (input temperature or measured temperature) is below span
adjustment value (input temperature or measured temperature), setting becomes disabled and
displays 'Er6'.
・
Setting range is 0 to 9999.
・
Setting of factory default is "2000".
[2-color adjustment display]
Tb
CONT
MEM
PEAK
[2-color adjustment display]
Tb
CONT
MEM
PEAK
Summary of Contents for IR-HA Series
Page 2: ......
Page 46: ...INST No INE 567 P1CE 38 12 2 External Dimensions Unit mm ...