INST.No.INE-567-P1CE
-19-
6.8 Memory Mode Selection
This setting is used to select data saving method, manual memory mode or interval memory in memory input
mode.
mAn
Manual memory mode: Measured data is saved when
ENT
key is pushed.
int
Interval memory mode: Measured data is saved by every set interval.
1) From setting mode display, push
SEL
key several times to
display "mmod" on the sub display.
2) Push
key or
key to select memory mode.
3) Blinking stops by pushing
ENT
key and the registration is completed.
6.9 Memory Interval Setting
This setting is used to set saving interval (sec.) of measured data on interval memory mode.
1) From setting mode display, push
SEL
key several times to
display "int" on the sub display.
2) Push
key or
key to change numeric value.
3) Blinking stops by pushing
ENT
key and the blinking digit
moves its position from lower place to the higher place and the
registration is completed.
Reference
Reference
Remark
Remark
This setting in only valid at memory input mode. (Refer to "8.2.1 Saving in Manual Memory Mode"
or "8.2.2 Saving in Interval Memory Mode".)
Setting of factory default is "mAn" (manual memory mode).
This setting in valid if interval memory is selected at memory input mode.
(Refer to "8.2.2 Saving in Interval Memory Mode")
・
Setting range is 1 to 7200sec.
・
Default setting is "60"sec.
[Memory interval setting display]
Tb
CONT
MEM
PEAK
[Memory mode selection display]
Tb
CONT
MEM
PEAK
Summary of Contents for IR-HA Series
Page 2: ......
Page 46: ...INST No INE 567 P1CE 38 12 2 External Dimensions Unit mm ...