Technical instructions
Cm
-SOL
8.3.x.1 T MAX tank 2
Setting the max temperature of the tank2.
Solar collectors are heating tank 2 to the temperature [T MAX tank 2]
after which solar heating of the tank 2 stops and switches to the next tank
according the priority (if exists).
If the collector cooling function is enabled and activated, tank
temperature can rise up to max. 90°C (or 95°C if TMAX tank is set to
90°C)
If the pool is set as the last tank in the configuration, max. temperature of
the pool can be set in following range:
8.3.2.5.1. Sensor lower
It is necessary to set (choose) address (input) of the connected sensor
upper (it is possible to connect sensor upper (it is possible to connect an
one free of 10 addresses, controller recommends input T3).
Sensor lower
Not exist
Not exist/T1/.../T10
8.3.2.5.2. Sensor type
If NTC sensor is installed, here must be changed from PT1000 to the
NTC.
Sensor type
PT1000
Factory settings
PT1000/NTC
installed and set sensor tank 1
lower
8.3.2.5. Sensor tank 1 lower
Sensor tank 1 lower is used:
- work of the collector pump.
- in case that back flow sensor isn’t installed, for energy meassurement
(meassurement is less precise than with back flow sensor).
- in case that sensor tank 1 upper isn’t installed, it takes over it’s
functions except additonal heating function with conventional heating
sources.
- at function of Collector cooling through the tank,
- at Collector antifreeze function,
- at Holiday option.
In this menu sensor address and type must be set.
T MAX tank 2
70
Facotry settings
min./max.
30 / 90
°C
T MAX tank X
28
15 / 40
°C
Installation, tank
example: configurated 1 tank (with 2
sensors), 1 flat plate collector,
return flow sensor, outdoor
sensor
Factory settings
selection
selection
unit.