3.x.
Pump/valve protection
The pump/valve protection follows the activity of the individual
output
(pump or valve) as due to
a long – term inactivity the pump/valve would
not block.
By setting the
off
inaction time (in the installation menu) it is
possible to determine the maximum inaction time of the
outpu
t, after
which
the controller activates the
output
for 60 seconds.
G
G
G
Pump/valve protection
OFF
ON/OFF
3.x.5. Skip legionella time
In this menu it is possible to switch on or off the skip legionella time
function for the Legionella protection.
If the function is switched on, and in the time interval between two
activation terms of the tank protection, the set temperature and the
desinfection time duration is reached, when the next activation term for
the protection arrives, the controller skips it and waits for the next term.
Skip legionella time
OFF
ON/OFF
3.x.6. Disinfection duration
Setting of time in which the water temperature on the upper sensor in the
tank must be above the set protection temperature in order to consider
that the disinfection was successfully performed.
Disinfection duration
15
min./max.
1 / 1440 min
jed.
3.x.7. Legionella recirculation
In this menu it is possible to switch on and off the recirculation operation
when the Legionella protection is active in order to disinfect the piping
(the condition is that the recirculation is configurated in the system).
When the conventional source starts up, also the recirculation pump
switches on, and operates
for as long as the disinfection time is set.
NOTE
:
The recirculation must exist and it is needed to switch it on in the
installation menu.
Legionella recirc.
OFF
ON./OFF
3.x.4. Choose source (source selection)
In this menu it is possible to select the conventional source with which
we would like to disinfect the tank according to the schedule and set
temperature. The selected source must be able to reach the set
temperature at the choosen time (in the menu only the configurated
conventional sources are listed).
Choose source
Electric heater
Electric heater/Boiler1/Boiler 2
primjer: konfigurirano 3 konvencionalna izvora
31
Technical instructions
Cm
-SOL
User menu, operation
Factory settings
selection
selection
Factory settings
Factory settings
selection
Factory settings
selection
Factory settings