38
REVO C
3PH from 30A to 40A
User’s manual
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Alarm
Function
Choose for which conditions the digital output
indicates alarm. The output always indicate an
alarm when the heat sink is over temperature. The
digital output is energized for normal operating
condition and de-energized when the power
controller is off or when there is an alarm.
Note!:
The power controller monitors for heater
break or short circuit condition only when
included in the option selected for Alarm Output
Function
1
34
Read
Write
Option
Description
Value
None
SCR is over temperature only
0
Heater Break
Heater Break or SCR is over temperature
1
Short Circuit
Short circuit or SCR is over temperature
2
HB / SC
Heater Break or Short circuit
3
These option may be
set via communication
only
Communication watchdog error
16
Communication watchdog error or Heater Break
17
Communication watchdog error or Short circuit
18
Communication watchdog error, Heater Break or Short circuit
19
DEFAULT:
Heater Break
1
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Retransmit
Choose which parameter is retransmitted by the
analog output
12
68
Read
Write
Option
Description
Value
None
Do not retransmit value
0
Set Point
Set point
15
V Output
RMS voltage output
10
I Output
RMS current output
11
Power
Average output power
12
DEFAULT:
Power
12