REVO C
3PH from 30A to 40A
User’s manual
35
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Prop band power
Set the gain for the main loop. A
smaller proportional band yields
a larger adjustment for a given
deviation
10%
0 to 255
%
26
Read
Write
Integral power
Set how aggressively the integral
part of the control algorithm acts.
A smaller settings yields a larger
adjustment for a given deviation over
a given time
50
0 to 255
27
Read
Write
Htr Break
sensitivity
Set the threshold of resistance that
activates the Heater Break alarm.
This setting is in percentage of the
nominal load resistance
100%
0 to 100.0
%
29
Read
Write
Htr Break delay
Set a delay between when the
resistance drops below the value
set for a heater break sensitivity
and when the heater break alarm
is indicated. This set increments of
50mSec
50 (2,5
sec)
0 to 255
(0 to 12,75
sec)
28
Read
Write
Logging
Enable or disable data logging on
the internal SD card
0
139
Read
Write
Option
Value
Off
0
On
1
DEFAULT:
Off
0
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Logging interval
Set how often data is logged
5 sec
0 to 255 sec
70
Read
Write