REVO C
3PH from 30A to 40A
User’s manual
33
9.4.2 Setup Menu
This section describes each item on the setup menu. Use this menu to configure the power controller for the
load.
The password to access this menu is 2.
Parameter Name
Description
Range
Unit
Modbus
Address
Par.
Type
Out Scale
Set the percentage by which the set point
is scaled. For example, if a 0 to 10V analog
input providing the set point is 5V and output
scaling is 80% then the effective set point is
40%
0 to 100.0
%
16
Read
Write
100
80
60
40
20
0
0 20 40 60 80 100
Input
Output Scaling = 100%
Output Scaling = 80%
Output Scaling = 40%
Scaled Set P
oint
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Nominal V
Set the nominal value for the line
voltage input
220V
0 to 1023
V
37
Read
Write
Nominal I
Set the nominal load current
Maximum
current
0 to 999.9
A
38
Read
Write
Remote SP
Choose the source for the remote
set point
61
Read
Write
Option
Value
Analog Input 1
0
Analog Input 2
1