40
REVO C
3PH from 30A to 40A
User’s manual
9.4.5 Communication Menu
This section describes each item on the communication menu. Use this menu to configure the communication
options.
The password to access this menu is 3.
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Port 1 Baud
Choose the baud rate for the primary serial port
2
30
Read
Write
Option
Value
9600
0
19200
1
38400
2
115200
3
DEFAULT:
38400
2
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Port 1 Address
Set the address for the primary serial
port
1
0 to 255
31
Read
Write
Port 2 Baud
Choose the baud rate for the primary
serial port
2
45
Read
Write
Option
Value
9600
0
19200
1
38400
2
115200
3
DEFAULT:
38400
2
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Watchdog
Enable or disable the watchdog on the primary
serial port
0
142
Read
Write
Option
Value
Off
0
On
1
DEFAULT:
Off
0