REVO C
3PH from 30A to 40A
User’s manual
39
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Retransmit Sale
Set the value of retransmitted
parameter to be represented by the
full scale of the analog output.
See the table below
0
0 to 9999
124
Read
Write
Retransmit
Recommended
Retransmission
Scaling
Resulting Signal
(4 to 20 mADC)
Resulting Signal
(0 to 20 mADC)
Resulting Signal
(0 to 10 VDC)
Max Value
Set Point
100
4mADC = 0%
20mADC = 100%
0mADC = 0%
20mADC = 100%
0VDC = 0%
10VDC = 100%
100.0
V Output
xV
where
x
is the
Nominal Line
Voltage
4mADC = 0V
20mADC = xV
0mADC = 0V
20mADC = xV
0VDC = 0V
10VDC = xV
999.9
I Output
xA
where
x
is the
Nominal Line
Current
4mADC = 0A
20mADC = xA
0mADC = 0A
20mADC = xA
0VDC = 0A
10VDC = xA
999.9
Power
100
4mADC = 0%
20mADC = 100%
0mADC = 0%
20mADC = 100%
0VDC = 0%
10VDC = 100%
100
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Retransmit Type
Choose type of signal for the retransmission
output
1
69
Read
Write
Option
Value
0-10V
1
4-20mA
0
0-20mA
2
DEFAULT:
0-10V
1
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Startup Display
Choose which parameter is displayed on the
home page at power-up
1
60
Read
Write
Option
Value
Current
0
Voltage
1
Power
2
DEFAULT:
Voltage
1