REVO C
3PH from 30A to 40A
User’s manual
37
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Digital In 1
Function
Choose how the signal detected by digital input 1
is used
2
32
Read
Write
Option
Description
Value
Enable
Enable power output
0
Voltage Feed-back
Use voltage feed-back when on
2
Local / Remote
Local when on / Remote when off
3
Set point Analog In 1/2
Select remote set point source: analog input 1 when off or analog
input 2 when on
5
Logging
Enable logging
6
FastEn
Fast Enable
8
DEFAULT:
Voltage Feed-back
2
SSR Input:
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc) 3HZ Max on time min. 100 ms
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Digital In 2
Function
Choose how the signal detected by digital input 2
is used
0
33
Read
Write
Option
Description
Value
Enable
Enable power output
0
Voltage Feed-back
Use voltage feed-back when on
2
Local / Remote
Local when on / Remote when off
3
Set point Analog In 1/2
Select remote set point source: analog input 1 when off or analog
input 2 when on
5
Logging
Enable logging
6
FastEn
Fast Enable
8
DEFAULT:
Enable
0
SSR Input:
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc) 3HZ Max on time min. 100 ms