57
<Checker Mode 2> Relay Operation Graph when #6 of F51 is Set
Step2
Step2 (HIGH)
Step3
Step1 (LOW)
Step1
Weight Value
SP1(LOW)
Output1
SP2(HIGH)
Output2
SP3 (OK)
Output 3
Lowest Limit NG
Output 4
Upper Limit NG
Output 5
Near Zero
Output 6
Note.
1. Required set value input: Step2 > Step1
2. Near zero output is according to the specified range in F57.
3. T3: Refer to F54 (Delay time of judgment-relay output)
T4: Refer to F55 (Operation time of judgment-relay output)
T5: Refer to F56 (Operation(ON) time of weighing NG relay output)
4. Relay Output
SP1(LOW): ON when the weight is stable and below the set value of Step1
SP2(HIGH): ON when the weight is stable and over the set value of Step2
SP3(OK): ON when the weight is stable and in between Step 1
≤
Step 2
Lowest Limit NG: ON during SP1 Output, adjust Output Time on T5
Upper Limit NG: ON during SP2 Output, adjust Output Time on T5
Near Zero: F57 Set Value
≥
0 Range Output
5. SP 1-4‘s status lamps in the front panel are operated in the same manner as the RELAY output.
T4
T5
T4
T5
T4
T3
T3
T3
Summary of Contents for CI-502A
Page 1: ... 2 ...
Page 9: ... 10 External Appearance and Dimensions External Appearance CI 502A CI 505A ...
Page 10: ... 11 Dimensions of the Product CI 502A CI 505A ...
Page 11: ... 12 Front Panel Descriptions CI 502A CI 505A ...
Page 27: ... 28 9 th Step Item MovebacktotheWeighingMode ...
Page 67: ... 68 Weight Data 8 byte a 13 5kg 1 3 5 b 135kg 1 3 5 c 135kg 1 3 5 ...
Page 74: ... 75 Sealing Method Sealing 1 Sealing the Indicator Sealing the Load Cell Connector ...
Page 83: ... 84 MEMO ...
Page 84: ... 85 MEMO ...
Page 85: ... 86 MEMO ...
Page 86: ... 87 MEMO ...
Page 87: ... 88 ...
Page 88: ... 89 ...