ZP3 Fire Panel User Guide
The status indicators are organized into the columns shown in Figure 8 on page
15, and the conditions shown in Table 7 below are indicated.
Table 7: Status indicator conditions
Indicator
Remarks
Power On
Indicates that the ZP3 panel has power, either from the mains or from the standby
battery.
Active
Indicates that a sounder, remote alarm, or extinguishing system has been
activated.
Fault
Indicates that a fault condition has been detected on a device or output. A system
fault indicates that a major fault exists in the panel.
Disabled
Indicates that a device or output has been deliberately disabled.
Delayed
Indicates that the activation of a sounder, remote alarm, or control output has
occurred, but that the actual operation of the output is in a delayed state.
Prealarm
Indicates that a zone or sensor is in a prealarm condition.*
Test
Indicates that the panel is in a test mode, which can be initiated either manually or
automatically, or that the commissioning key is ON.
* If the system is set up for coincidence detection (two active detectors are required to raise an
alarm) then this LED indicates when one of these detectors is active. A fire alarm is triggered if a
second detector confirms the condition.