background image

Page 1 of 8 

  D A T A   S H E E T

 V85005-0135

 

Not to be used for installation purposes.

  Issue 1.1

Kidde Catalog 

u

 Small Building Fire Alarm Solutions

11-17-16

Technology that saves lives

Overview

Kidde brand intelligent life safety systems offer the power of high-
end intelligent processing in configurations that deliver uncompli-
cated solutions for small to mid-sized applications. With intelligent 
detection, electronic addressing, automatic device mapping, 
optional Ethernet

®

 connectivity, and a full line of easily-configured 

option cards and modules, these flexible systems offer versatility 
that benefits building owners and contractors alike.

The VS1

 provides one Class A or Class B intelligent device loop 

that supports up to 64 device addresses, and two Class B Notifi-
cation Ap pliance Circuits (NACs). Optional Class A device wiring is 
available with the use of a module.

The VS4

 

provides one Class A or Class B intelligent device 

loop that supports up to 250 device addresses. Loop controller 
modules may be added in combination to expand total system 
capacity in 250-point increments to up to 1,000 device addresses. 
VS4 panels include four NACs that may be wired for either Class A 
or Class B operation.

The RZI16-2

 module adds even more capacity to VS installations 

by adding up to 16 conventional device circuits and two additional 
notification appliance circuits. This makes them ideal retrofit solu-
tions that can accommodate new intelligent detectors, as well as 
existing conventional devices.

VS Series supports a wide range of high-end features, including:

•  Intelligent modules, detectors, and bases
•  GSA-REL Releasing Modules
•  R-Series remote annunciators
•  Integrated Carbon Monoxide gas sensing with V-PCOS de-

tectors including distinct audible signaling

Features

•  Auto-programming speeds installation time
•  Supports V-Series intelligent modules and detectors
•  Form C contacts for alarm and trouble, Form A for supervisory
•  Electronic addressing with automatic device mapping
•  Optional Ethernet port for diagnostics, programming and a 

variety of system reports

•  Two programmable switches with LEDs and custom labeling
•  Supports Genesis horn silence over two wires, and UL 

1971-compliant strobe synchronization

•  Supports GSA-REL releasing module for fire suppression
•  Class B or Class A wiring
•  Ground fault detection by module
•  Supports up to eight serial annunciators, (LCD, LED-only, and 

graphic interface)

•  Can use existing wiring for most retrofit applications
•  Upload/download remotely or locally
•  Two-level maintenance alert reporting
•  Pre-alarm and alarm verification by point
•  Adjustable detector sensitivity
•  4 x 20 character backlit LCD display
•  Optional earthquake hardening: seismic Importance Factor 1.5
•  Standalone operation
•  Transmission test frequency by hour

Intelligent Fire 

Alarm Systems

VS1, VS4

7165-1657: 

0244

S3000

COA 6229

Содержание Kidde VS1

Страница 1: ...and two additional notification appliance circuits This makes them ideal retrofit solu tions that can accommodate new intelligent detectors as well as existing conventional devices VS Series supports...

Страница 2: ...ckly gets the panel operational using factory default settings Basic zone and point settings can be programmed through the front panel interface so the system is up and running in no time For more adv...

Страница 3: ...andby batteries 1 2 3 4 5 6 7 8 9 10 11 12 13 00 00 00 01 01 07 Four Class B or two optional Class A NACs Up to 20 000 feet of wiring per loop Four Class B or two optional Class A NACs Optional 10 A o...

Страница 4: ...individually configured for continuous temporal synchronized and coded output Specifications VS4 VS1 Circuit Type 4 Class B or 2 Class A 2 Class B or 2 Class A with SA CLA module Voltage 24 VFWR Curre...

Страница 5: ...itch used to select the default Relay or NAC output device type Device types other than the default are accomplished through programming RZI16 2 Specifications Voltage 24V Aux nominal Supervisory curr...

Страница 6: ...priority alarm supervisory trouble and monitor Activations are transmitted before restora tions The SA DACT is installed on the plastic assembly and connects to the main circuit board via a ribbon cab...

Страница 7: ...y 500 mA Output 28 3 to 21 9 VDC special application Note For a list of compatible devices see the VS1 and VS4 Series Compatibility List P N 3102354 EN Loop circuit Maximum loop resistance 66 Maximum...

Страница 8: ...One loop system one 64 point loop installed 110v gray door English Canada VS1 GL F One loop system one 64 point loop installed 110v gray door French Canada VS1 G PG One loop system with one 64 point...

Отзывы: