![background image](http://html.mh-extra.com/html/carrier/ziton-zp3/ziton-zp3_user-manual_2562680042.webp)
34
ZP3 Fire Panel User Guide
Record keeping
The operator should maintain a logbook (see document 503-1842ZE-0-02) at the
control panel. A record of all alarms, events, checks, tests, and repairs should be
entered in this logbook.
Routine maintenance
Note:
Occupants of the building and anyone receiving remote alarm signals,
such as the fire department, must be informed before starting with the test or
routine maintenance. They must also be informed when the test or routine
maintenance is complete. No alarms should be activated before notification has
taken place.
Caution:
External systems connected to the fire system, such as fire
extinguishing systems, air conditioning systems, or lifts must be temporarily
disabled or disconnected
before
testing or routine maintenance takes place.
WARNING:
All disconnected or disabled systems must be reconnected and
enabled at the end of testing.
Daily checks
Do the following checks every day:
1. Check that the green Power On indicator is illuminated. All other LEDs should
be off except the common Disabled LED (depending on the system status,
e.g. day mode) and the panel should be silent. The display should show the
time and date only.
2. If the panel is indicating a fault alarm, contact the maintenance staff and
arrange for the fault to be rectified.
3. Make sure the logbook (document 503-1842ZE-0-02) is kept up-to-date.
Check that all faults recorded in the logbook the previous day have been
attended to.
4. Make sure that the correct time and date is displayed on the ZP3 panel. If not,
correct the time and date as described under “Menu structure” on page 30.
Weekly checks
Notes
• Contact the alarm-receiving centre immediately before starting this test to
inform them of the test thus preventing unnecessary response to an alarm.
• Refer to the appropriate section of this manual for more information about
ZP3 panel operation.
• The following guidelines are based on the recommendations provided by
BS5839-1 2002.
Summary of Contents for Ziton ZP3
Page 1: ...ZP3 Fire Panel User Guide P N 503 1160ZE U 14 ISS 08JUL21 ...
Page 44: ......