ZP3 Fire Panel User Guide
15
Sound Alarms button
Press the Sound Alarms button to activate all the sounders in the building.
This can be done, for example, to sound a general alert or to restore sounders
that were silenced.
Restore Disabled Alarms button
In Software version 3.10 and earlier, press the Restore Disabled Alarms button to
restore disabled sounders.
In Software version 3.11 and later: press the Restore Disabled Alarms Button to
toggle between Disable All Sounders and Enable All Sounders, as indicated by
the Sounders Disabled LED.
Maintenance staff can disable alarm sounders for routine maintenance. If a fire
alarm occurs while these devices are disabled, the sounders do not work.
Pressing the Restore Disabled Alarms button to enter the Enable All Sounders
state, cancels (overrides) any programmed delays, and lets the system respond
to the alarm immediately. (Pressing this button doesn’t create an alarm, but
simply restores alarm devices to let them operate correctly during an alarm.)
Status indicators
See Figure 8 below. The status indicators provide a comprehensive overview of
the current status of the complete fire detection system.
Figure 8: Status indicators
DISABLEDDELAYED PRE-ALM
TEST
ENABLE
CONTROL
ON
OFF
FAULT
ACTIVE
POWER ON
SYSTEM
NIGHT
ZONE
DAY
POINT
MORE TIME
SOUNDERS
REMOTE ALARM
CONTROL OUTPUTS
RESTORE
DISABLED
ALARMS
Status indicators
The status indicators categorize the system into the elements shown in Table 6
below.
Table 6: System categorization
Name
Description
System
The panel, including the CPU.
Zone
A grouping of sensors or other line devices.
Point
A single line device, such as a sensor, call point, or sounder.
Sounders
Alarm devices, including electronic sirens, bells, etc.
Remote alarm
Alarm to a Remote Manned Centre (RMC), such as a Fire Brigade.
Control outputs
Output devices internally mapped as Control Outputs used to control building
systems such as extinguishing control systems, air conditioning systems,
etc.