26
ZP3 Fire Panel User Guide
The auto-enable feature (also called
disable for a period
) is detailed in Table 13
below.
Table
13
: Auto-enable (disable for a period)
Menu path
Maintenance > Edit or View Disabled (Points, Zones)
Purpose
This menu lets you temporarily disable an address in half hour intervals. This
allows multiple zones and line input devices to be disabled but not panel or
panel bus outputs. After the period expires, the address enables again
automatically. The menu allows the user to select Auto Enable, after a
disablement period configurable from 30 minutes to 12 hours.
Points
To auto enable any point select Edit Disabled from the Maintenance menu.
Select the point to be auto enabled and select Auto, using the arrows to scroll
up or down to set the required time period. Use the scroll feature to display the
next or previous point to be disabled. Use the Enter key to confirm the
selection.
Zones
To auto enable zones select Edit Disabled from the Maintenance menu.
Select the zones to be auto enabled and select Auto, using the arrows to
scroll up or down to set the required time period. Use the Enter key to confirm
the selection.
Notes: The disabled status can be overridden by:
• A local enable event from the local panel
• A remote enable event from a remote panel via the peer-to-peer network
• A change over from day to night mode may extend the disabled period to
coincide with the Disable by Night option.
In the case of dual or multiple sensor detectors, both smoke and heat
elements are disabled.
Other alarms
Alarms that are not categorized as fires, faults, or disablements are shown as
Other alarms, and are displayed on the panel as described in Table 14 below.
The actions carried out upon receipt of one of these alarms are determined by
two things; the nature of the alarm and the procedures at the site where the
system is installed. The following are generic guidelines only.
Table 14: Other alarms — annunciation and alarm
Description
Remarks
Common Other LED
Illuminated.
Text display
Zone screen showing details of the zone or element with the alarm,
and a general description of the alarm.
Panel buzzer
Sounding continuously.
Building sounders
Not sounding (typically). Depends on your system configuration.
Auxiliary functions
Active, if configured to operate (e.g. calling a remote manned centre,
calling maintenance staff, etc.).
Status indicators
Illuminated to show the affected system element. In addition, the LEDs
indicate which functions are active.