6
ZP3 Fire Panel User Guide
Total Loss of Power alarm
The ZP3 panel is fitted with a Total Loss of Power alarm feature. This feature is a
prewired, independent circuit that turns on the Common Fault and System Fault
LEDs and sounds a buzzer in the event of total loss of power. This condition
occurs when the mains power has been lost and the battery has been depleted
to the extent that load shedding has occurred, prior to the entire panel being shut
down. In this state, the display is shut down, the fault LEDs are on, and the panel
buzzer is sounding.
Accessories and peripherals
In addition to the ZP-loop devices, a range of accessories and peripheral devices
is available to provide all the elements of a complete system. The ZP3 panel,
when fitted with the software shown in the specification supports the following
accessories and peripherals.
Table 4: Supported accessory and peripheral models
Number
Description
ZP3-RDU
Remote display unit (mini)
ZP3-RDU
Remote display unit (full-function)
ZP3-RAC
Remote I/O accessory cabinet
ZP3-RL8
Addressable relay board, 8-way
ZP3-MA8
Addressable sounder driver board (monitored), 8-way
ZP3-MIP8
Addressable input board, 8-way
ZP3-OP24
Addressable transistor output board, 24-way
ZP3-SCB-D
Control bus driver board
ZP3-SCB-R
Control bus receiver board
ZP3-NET1
Network driver board, single
ZP3-SB232
Serial communications board, RS-232
ZP3FBR-2-B1
Fireman’s interface panel (Swedish)
ZP3FBR-2-R1
Fireman’s repeater panel
ZP3AB-NLM2
Network loop monitor
ZP471A
Radio loop module (receive only)
ZP472A
Radio loop module (transmit and receive)
ZP3AB-MD3
Modem kit
Later versions of software may support additional or different devices. If in doubt,
check with your local supplier.