![background image](http://html.mh-extra.com/html/carrier/ziton-zp3/ziton-zp3_user-manual_2562680022.webp)
14
ZP3 Fire Panel User Guide
View Points button
Press the View Points button to access the Device screen, which shows the
alarms by device (point), together with their address, location, device type, the
nature of the alarm, and the programmed device message.
Help button
Press the Help button to display on-screen operating instructions for the ZP3
panel. Scroll through these instructions using the Up or Down buttons.
Main operating controls
See Figure 7 below. Five main controls are used to operate the system. Each
button is described below.
Figure 7: Main operating controls
ACCEPT
MUTE
BUZZER
RESET
FIRE
FAULT
DISABLED
OTHER
SILENCE
ALARMS
SOUND
ALARMS
DISABLED DELAYED PRE-ALM
TEST
ENABLE
CONTROL
ON
OFF
FAULT
ACTIVE
POWER ON
SYSTEM
NIGHT
ZONE
DAY
POINT
MORE TIME
SOUNDERS
REMOTE ALARM
CONTROL OUTPUTS
RESTORE
DISABLED
ALARMS
Accept button
Reset button
Sound Alarms button
Silence Alarms button
Restore Disabled
Alarms button
Day/Night button
Restore Disabled
Alarms button
Accept button
Press the Accept button after receipt of an alarm. This causes the illuminated
indicators to go steady, and silences the panel buzzer.
Reset button
Press the Reset button to clear all alarms from the system and restore the panel
to a normal state with no alarms.
All displayed alarms are removed, and all illuminated indicators are switched off.
Sounders (unless programmed to be dynamic) are switched off, and the remote
manned centre alarm is restored to a normal state with no alarms. If any sensors,
call points, or other devices still sense fire, smoke or a fault, then the panel
returns to an alarm condition.
Silence Alarms button
Press the Silence Alarms button to silence (turn off) the sounders.
An alarm condition activates certain sounders throughout the building. Which
sounders are activated depends on the configuration of your system. After
pressing the Silence Alarms button, the Sounders Silenced indicator above the
button illuminates.