ZP3 Fire Panel User Guide
27
Description
Remarks
Delayed functions
Delayed LED illuminated for those functions that are programmed to
operate in response to the alarm, and are configured for delayed
operation. These could be remote centre alarms or control functions.
Types of alarm
Other alarms can be categorized as shown in Table 15 below).
Table 15: Other alarms — types of alarm
Category
Description
Prealarms
Prealarms and alert alarms from smoke sensors and high-sensitivity
detectors.
Security alarms
Alarms from security interface devices.
Non-fire alarms
Alarms from interface devices used for monitoring non-fire functions.
Service
Services, maintenance, and preservice indications.
Operator action
1. Press the Accept button to acknowledge the alarm.
This silences the panel buzzer, and causes the flashing alarm indicators to go
steady.
Do not press the Reset button.
2. Take action appropriate for the type of alarm.
The type of alarm determines the action to take. For example, a “Prealarm”
could indicate a small quantity of smoke, and might require prompt attention.
3. Record the action taken in the logbook.
4. After resolving the alarm, press the Reset button.
The system restores to its normal state.