KGAET0201ETK: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

9

WARNING

!

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected

to the venting system being placed into operation could result in carbon

monoxide poisoning or death.

The following steps shall be followed for each appliance connected to

the  venting  system  being  placed  into  operation,  while  all  other

appliances connected to the venting system are not in operation:

1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as

required in the National Fuel Gas Code, ANSIZ223.1/NFPA 54 or

the  CSA B149.1 Natural Gas and Propane Installation Code and

these  instructions.  Determine  that  there  is  no  blockage  or

restriction, leakage, corrosion and other deficiencies, which could

cause an unsafe condition.

3. As far as practical, close all building doors and windows and all

doors  between  the  space in  which the appliance(s)  connected to

the venting system are located and other spaces of the building.

4. Close fireplace dampers.
5. Turn  on  clothes  dryers  and  any  appliance  not  connected  to  the

venting system. Turn on any exhaust fans, such as range hoods and

bathroom exhausts, so they are operating at maximum speed. Do

not operate a summer exhaust fan.

6. Follow  the  lighting  instructions.  Place  the  appliance  being

inspected  into  operation. Adjust  the  thermostat  so  appliance  is

operating continuously.

7. Test for spillage from draft hood equipped appliances at the draft

hood relief opening after 5 minutes of main burner operation. Use

the flame of a match or candle.

8. If improper venting is observed during any of the above tests, the

venting system must be corrected in accordance with the National

Fuel  Gas  Code,  ANSIZ223.1/NFPA  54  and/or  CSA  B149.1

Natural Gas and Propane Installation Code. 

9. After it has been determined that each appliance connected to the

venting  system  properly  vents  when  tested  as  outlined  above,

return doors, windows,  exhaust  fans,  fireplace  dampers and  any

other gas-fired burning appliance to their previous conditions of

use.

Summary of Contents for KGAET0201ETK

Page 1: ...r Follow the manufacturer s instructions in the use of primer and cement and never use primer or cement beyond its expiration date The safe operation as defined by ULC S636 of the vent system is based...

Page 2: ...rainage system and possibly the living space See Fig 3 Application to Combustion Air Inlet Piping Systems This Trap Kit may used to help prevent liquid moisture from the inlet piping system from enter...

Page 3: ...be either away from trap vent side or toward trap combustion air side curve of vent tee must be positioned toward termination toward major flow of condensate except as shown in Fig 2 i When larger di...

Page 4: ...t and transition to the pipe diameter required in the vertical portion of the pipe after the tee WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow these warnings could result in personal inju...

Page 5: ...d listed to ULC S636 3 Not all materials below may be approved or listed to ULC S636 4 Royal Pipe and IPEX are approved suppliers of ULC S636 pipe fittings cements and primers 5 Factory accessory conc...

Page 6: ...PLUG THESE PORTS A OPEN DOWNFLOW ORIENTATION B PLUG THESE PORTS A OPEN HORIZONTAL RIGHT ORIENTATION A OPEN B PLUG THESE PORTS HORIZONTAL LEFT ORIENTATION Representative drawing only some models may va...

Page 7: ...llations must comply with regulations of local building heating plumbing or other codes in effect in area where installation is made Complete the installation of the drainage system as follows 1 Dry f...

Page 8: ...te 7 Listen for gurgling noises in the venting and drainage systems This is an indication that there are dips in the piping system or that the traps are not operating properly Correct the conditions a...

Page 9: ...g doors and windows and all doors between the space in which the appliance s connected to the venting system are located and other spaces of the building 4 Close fireplace dampers 5 Turn on clothes dr...

Page 10: ...y in appearance H G SLOPE UP TO TERMINATION 1 4 IN PER FOOT Two inch pipe shown When another size pipe is used discard the 2 in tee in the kit and use a field supplied tee that is the same diameter as...

Page 11: ...ISTS G B A AIR FLOW H SLOPE UP TO TERMINATION 1 4 IN PER FOOT Two inch pipe shown When another size pipe is used discard the 2 in tee in the kit and use a field supplied tee that is the same diameter...

Page 12: ...PIPIING See NOTES in Figure 1 COMBUSTION AIR INLET PIPE MAY TERMINATE IN WELL VENTILATED CRAWL SPACE VENTILATED COMBUSTION AIR OR EXTERNAL TO STRUC TURE TRAP KIT MAY ALSO BE APPLIED SLOPE UP TO TERMIN...

Page 13: ...rnace L12F029 Fig 12 Combustion Air and Vent Pipe Diameter Transition Location and Elbow Configuration Representative drawing only some models may vary in appearance TO CODE APPROVED DRAIN OR CONDENSA...

Page 14: ...rrier Company Edition Date 04 20 Catalog No AG KGAET 06 Replaces AG KGBET 01 KGAET0201ETK Installation Instructions Manufacturer reserves the right to change at any time specifications and designs wit...

Reviews: