background image

KGAET0201ETK: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

8

3. Dry fit remaining drainage system piping as shown in 

Fig. 1

Fig. 2

and   

Fig. 4

  through 

Fig. 8

,  as  appropriate  for  the  specific

installation requirements, using field-supplied components.

4. IF ALLOWED BY LOCAL CODE, it is recommended that a short

piece of clear tubing (6-in./0.2 M) be applied near the exit of each

trap to allow observation of correct drain trap operation.

5. Support all drainage system piping as needed, and in compliance

with local codes.

6. Verify that all drainage piping is sloped toward the open drain or

condensate sump pump.

7. Cement  external  condensate  drain  trap  to  the  trap-tee  and

connection adapters, if any. 

8. Cement all remaining drainage system piping as required.

System Commissioning and Checkout

Follow these steps to verify proper operation of the trap and drainage

system:

1. IF ALLOWED BY LOCAL CODE, it is recommended that a short

piece of clear tubing (6-in./15 cm) be applied near the exit of each

trap to allow observation of correct drain trap operation.

2. Prime the furnace internal condensate drainage trap per the furnace

installation instructions. Collect or observe excess priming water at

the end of the drainage piping system to verify that the trap is fully

primed.

3. Prime  the  Trap  Kit  connected  to  the  venting  system  by  slowly

pouring at least 32-oz. (1 liter) of water into the vent termination.

Collect or observe excess priming water at the end of the drainage

piping system to verify that the trap is fully primed.

4. Prime  the  Trap  Kit  connected  to  the  combustion-air  inlet  piping

system  (IF  USED)  by  slowly  pouring  at  least  32-oz.  (1  liter)  of

water into the combustion air inlet at the vent termination. Collect

or observe excess priming water at the exit of the drainage piping

system to verify that the trap is fully primed.

5. Once the furnace has been completely installed per the instructions

supplied with the furnace, run the furnace for at least one hour to

verify that all drainage systems are operating properly.  Collect or

observe  condensate  drainage  at  the  exit  of  the  drainage  piping

system to verify that the traps are fully primed and that the drain

system is not blocked.

6. If the clear tubing has been applied to the drainage system, observe

that EACH trap in the system is draining properly. NOTE that the

combustion-air  inlet  piping  system  will  likely  NOT  produce

condensate.

7. Listen for gurgling noises in the venting and drainage systems. This

is an indication that there are dips in the piping system, or that the

traps are not operating properly. Correct the conditions as needed.

8. If  there  are  water  gurgling  or  sloshing  sounds  coming  from  the

inducer housing, this is an indication that not all of the vent piping

is sloped AWAY from the furnace and toward the Trap Kit. Correct

the conditions as needed.

9. Shut down the furnace.
10. Once all drainage checks and verifications have been made, return

the furnace to its normal operating condition.

11. Perform  the  venting  system  checklist  as  shown  in  the  following

WARNING box.

WARNING

!

CARBON MONOXIDE POISONING HAZARD

Failure  to  follow  these  warnings  could  result  in  personal  injury  or

death.

The Internal Drain Trap Plug MUST BE APPLIED to the vent side of

the  collector box  trap  connection  of  the  furnace  when the  trap  kit  is

applied to the vent/exhaust piping system. Failure to do this may result

in vent gasses being released into the living space.

Failure  to  use  a  properly  constructed  trap(s)  or  NOT  water-priming

trap(s) before operating furnace may allow positive pressure vent gases

to  enter  the  structure  through  drain  tube.  Vent  gases  contain  carbon

monoxide which is tasteless and odorless.

WARNING

!

CARBON MONOXIDE POISONING HAZARD

Failure  to  follow  these  warnings  could  result  in  personal  injury  or

death.

If water vapor (fog) rather than liquid condensate is observed exiting

the  drain  port  any  of  the  traps,  that  MAY  be  an  indication  that

combustion gasses are escaping through the drain system.

• RECHECK that all traps are properly water-primed. 

• RECHECK that the Internal Drain Trap Plug is properly inserted into

the internal condensate drain trap in the furnace (see 

Fig. 3

).

• DO NOT operate the furnace until it is verified that all condensate

drain traps are operating properly.

Failure  to  use  a  properly  constructed  trap(s)  or  NOT  water-priming

trap(s) before operating furnace may allow positive pressure vent gases

to  enter  the  structure  through  drain  tube.  Vent  gases  contain  carbon

monoxide which is tasteless and odorless.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution could result in intermittent unit operation.
When the Internal Drain Trap Plug is used, the inducer housing may fill

with condensate if any of the vent piping that is external to the furnace

is sloped toward the furnace.

CAUTION

!

FIRE HAZARD

Failure to follow this warning could result in personal injury, death or

property damage. 
Solvent cements and primers are combustible. Keep away from heat,

sparks  and  open  flame.  Use  only  in  well-ventilated  areas.  Avoid

breathing in vapor or allowing contact with skin or eyes.

Summary of Contents for KGAET0201ETK

Page 1: ...r Follow the manufacturer s instructions in the use of primer and cement and never use primer or cement beyond its expiration date The safe operation as defined by ULC S636 of the vent system is based...

Page 2: ...rainage system and possibly the living space See Fig 3 Application to Combustion Air Inlet Piping Systems This Trap Kit may used to help prevent liquid moisture from the inlet piping system from enter...

Page 3: ...be either away from trap vent side or toward trap combustion air side curve of vent tee must be positioned toward termination toward major flow of condensate except as shown in Fig 2 i When larger di...

Page 4: ...t and transition to the pipe diameter required in the vertical portion of the pipe after the tee WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow these warnings could result in personal inju...

Page 5: ...d listed to ULC S636 3 Not all materials below may be approved or listed to ULC S636 4 Royal Pipe and IPEX are approved suppliers of ULC S636 pipe fittings cements and primers 5 Factory accessory conc...

Page 6: ...PLUG THESE PORTS A OPEN DOWNFLOW ORIENTATION B PLUG THESE PORTS A OPEN HORIZONTAL RIGHT ORIENTATION A OPEN B PLUG THESE PORTS HORIZONTAL LEFT ORIENTATION Representative drawing only some models may va...

Page 7: ...llations must comply with regulations of local building heating plumbing or other codes in effect in area where installation is made Complete the installation of the drainage system as follows 1 Dry f...

Page 8: ...te 7 Listen for gurgling noises in the venting and drainage systems This is an indication that there are dips in the piping system or that the traps are not operating properly Correct the conditions a...

Page 9: ...g doors and windows and all doors between the space in which the appliance s connected to the venting system are located and other spaces of the building 4 Close fireplace dampers 5 Turn on clothes dr...

Page 10: ...y in appearance H G SLOPE UP TO TERMINATION 1 4 IN PER FOOT Two inch pipe shown When another size pipe is used discard the 2 in tee in the kit and use a field supplied tee that is the same diameter as...

Page 11: ...ISTS G B A AIR FLOW H SLOPE UP TO TERMINATION 1 4 IN PER FOOT Two inch pipe shown When another size pipe is used discard the 2 in tee in the kit and use a field supplied tee that is the same diameter...

Page 12: ...PIPIING See NOTES in Figure 1 COMBUSTION AIR INLET PIPE MAY TERMINATE IN WELL VENTILATED CRAWL SPACE VENTILATED COMBUSTION AIR OR EXTERNAL TO STRUC TURE TRAP KIT MAY ALSO BE APPLIED SLOPE UP TO TERMIN...

Page 13: ...rnace L12F029 Fig 12 Combustion Air and Vent Pipe Diameter Transition Location and Elbow Configuration Representative drawing only some models may vary in appearance TO CODE APPROVED DRAIN OR CONDENSA...

Page 14: ...rrier Company Edition Date 04 20 Catalog No AG KGAET 06 Replaces AG KGBET 01 KGAET0201ETK Installation Instructions Manufacturer reserves the right to change at any time specifications and designs wit...

Reviews: