![background image](http://html1.mh-extra.com/html/carrier/kgaet0201etk/kgaet0201etk_installation-instructions-manual_2563797006.webp)
KGAET0201ETK: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
L12F018
Fig. 4 – Location of Collector Box Vent Connection Trap Plug
(Only used when Trap Kit is used on the Vent Pipe)
Venting and Combustion Air System Layout and
Installation
NOTE:
Slope vent pipes a minimum of 1/4-in. per linear ft.
(20mm/meter) toward the Vent/Exhaust Pipe External Trap Kit with no
sags between hangers. DO NOT slope the vent pipes toward the furnace
when using the trap kit on the vent/exhaust piping system.
NOTE:
Slope the combustion-air inlet pipes a minimum of 1/4-in. per
linear ft. (20mm/meter) toward the exterior of the structure or insert a
second Trap Kit at the lowest point of the combustion-air inlet piping
system, within 24-in. (0.6 M) of the furnace.
B
ï
PLUG
THESE
PORTS
A
ï
OPEN
UPFLOW
ORIENTATION
B
ï
PLUG
THESE
PORTS
A
ï
OPEN
DOWNFLOW
ORIENTATION
B
ï
PLUG
THESE
PORTS
A
ï
OPEN
HORIZONTAL
RIGHT
ORIENTATION
A
ï
OPEN
B
ï
PLUG
THESE
PORTS
HORIZONTAL
LEFT
ORIENTATION
Representative drawing only, some models may vary in appearance
NOTE
:
A. The lower
ï
most low
ï
side “pivot” port on the collector box is always left open for the internal drain trap.
B. Insert plugs into BOTH of the high
ï
side ports, ONLY when the Trap Kit is applied to the vent pipe.
C. DO NOT plug the trap port when the Trap Kit is used only for the combustion air pipe.
NOTICE
!
Follow all vent sizing and selection instructions that are included in the
Venting section of the furnace installation instructions.
The Equivalent Length of the Vent/Exhaust Pipe External Trap Kit
should be assumed to be 15 feet (5 M) of straight length of PVC/ABS
DWV pipe.
CAUTION
!
UNIT OPERATIONAL HAZARD
Failure to follow this caution may result in intermittent unit operation.
This kit is intended to be located at the lowest point in the vent system
and no more than 24-in. (0.6M) horizontally from where the vent exits
the furnace to achieve proper drainage.