background image

KGAET0201ETK: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

7

Vent Located in Unconditioned Space

Vent Pipe and Condensate Drain Protection

Freezing  condensate  in  condensate  traps  and  drain  lines  may  cause

cracks, and possible water damage may occur. Refer to the Maximum

Allowable Exposed Vent Lengths in Unconditioned Space limitations in

the furnace installation instructions.

Layout and Dry Fit Venting System

Layout and install the venting and/or combustion-air inlet system(s) as

follows:

1. Determine  the  best  location  for  kit  components. They  should  be

installed as close to furnace as possible (see 

Fig. 4

 through 

Fig. 8

for examples).

2. Size  the  venting  system  per  the  instructions  provided  with  the

furnace.

3. Dry-fit  and  assemble  vent/exhaust  and/or  combustion-air  inlet

piping  per  the  instructions provided with  the furnace, except that

the Trap Kit is placed at the lowest point of the vent/exhaust and/or

combustion-air  inlet  piping  system  (see 

Fig. 4

  through 

Fig. 8

  for

examples).

4. Cut section of vent/exhaust pipe to attach the trap-tee fitting, using

the examples in 

Fig. 1

Fig. 2

 and  

Fig. 2

 through 

Fig. 8

.

NOTE: 

Position vent-tee fitting such that curved portion is as shown in

Fig. 1

  and 

Fig. 2

  to  ensure  proper  vent/exhaust  and/or  combustion-air

inlet pipe draining.

5. Dry fit  the trap-tee  fitting into  the venting  and/or combustion-air

inlet piping system.

6. Verify  the  proper  slope  of  the  entire  vent/exhaust  and/or

combustion-air  inlet  piping  system  to  the  trap-tee(s).  ALL

vent/exhaust piping between the furnace and the Trap Kit should be

sloped DOWN and AWAY from the furnace.

7. Cement all vent and/or combustion-air inlet piping in place, per the

instructions provided with the furnace.

Drainage System Layout and Installation

The furnace, indoor coil, and humidifier drains may be combined and

drained  together.  The  indoor  coil  drain  must  have  an  external,

field-supplied trap prior to the furnace drain connection, and/or spill into

an open stand pipe (see 

Fig. 1

 

Fig. 2

). All drain connections (furnace,

indoor coil, or  humidifier) must be terminated into an  open  or vented

drain  as  close  to  the  respective  equipment  as  possible  to  prevent

siphoning  of  the  other  equipments’  drains.  See  equipment  installation

instructions for more information.
Outdoor draining of the furnace is permissible if allowed by local codes.

Use the accessory acid neutralizer kit as required by the application (to

protect shrubs, etc.), or as required by local codes.

Condensate is not to be drained onto crawlspace floor from furnace or

external  trap.  Installations  must  comply  with  regulations  of  local

building,  heating,  plumbing,  or  other  codes  in  effect  in  area  where

installation is made.
Complete the installation of the drainage system as follows:

1. Dry fit the external condensate drain trap supplied with the kit into

the vent trap-tee fitting. Apply field-supplied fittings as required if

the 2-in. (50mm) trap-tee supplied with the kit was not used.

2. Position the external condensate drain trap as required to match to

the condensate drainage piping system.

CAUTION

!

UNIT OPERATIONAL HAZARD

Failure to follow this caution may result in intermittent unit operation.
The  combustion-air  inlet  piping  system  must  not  have  any  sections

where  moisture  may  collect  and  block  the  flow  of  combustion  air

through  the  piping  system.  If  water  does  block  the  inlet  pipes,  the

furnace will not operate, or operate intermittently.

CAUTION

!

UNIT OPERATIONAL HAZARD

Failure to follow this caution may result in intermittent unit operation.
Unit must not be installed, operated, and then turned off and left in an

unoccupied structure during cold weather when temperature drops to

32°F (0°C) and below unless drain traps and drain lines have adequate

freeze  protection.  See  Service  and  Maintenance  Instructions  for

winterizing procedure.

CAUTION

!

UNIT OPERATIONAL AND PROPERTY DAMAGE 

HAZARD

Failure to follow this caution may result in intermittent unit operation,

and  may  cause  frozen  and/or  burst  indoor  plumbing  and  property

damage.
Caution should be taken to prevent condensate trap(s) and drain line(s)

from  freezing. Ambient  temperatures  below  32°F  (0°C)  may  freeze

drain pipe and prohibit draining. If freeze protection is required, use a

self-regulating, shielded, and waterproof heat tape rated at 3 to 6 watt

per ft. (10 to 20 watt per meter) at 120v and 40°F (4°C). See Installation

Instructions supplied with accessory condensate trap heater, accessory

heat tape, or heat tape manufacturer’s recommendations.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution could result in intermittent unit operation.
The inducer housing may fill with condensate if any of the vent piping

that is external to the furnace is sloped toward the furnace.

WARNING

!

FIRE HAZARD

Failure to follow this warning could result in personal injury, death or

property damage. 

Solvent cements and primers are combustible. Keep away from heat,

sparks  and  open  flame.  Use  only  in  well-ventilated  areas.  Avoid

breathing in vapor or allowing contact with skin or eyes.

CAUTION

!

PERSONAL INJURY OR PROPERTY DAMAGE 

HAZARD

Failure to follow this caution may result in personal injury or property

damage.
Caution should be taken to prevent draining where slippery conditions

may cause personal injuries.
Excessive condensate drainage in open areas may cause saturated soil

conditions  which  may  result  in  damage  to  plants  and  building

foundations.

Summary of Contents for KGAET0201ETK

Page 1: ...r Follow the manufacturer s instructions in the use of primer and cement and never use primer or cement beyond its expiration date The safe operation as defined by ULC S636 of the vent system is based...

Page 2: ...rainage system and possibly the living space See Fig 3 Application to Combustion Air Inlet Piping Systems This Trap Kit may used to help prevent liquid moisture from the inlet piping system from enter...

Page 3: ...be either away from trap vent side or toward trap combustion air side curve of vent tee must be positioned toward termination toward major flow of condensate except as shown in Fig 2 i When larger di...

Page 4: ...t and transition to the pipe diameter required in the vertical portion of the pipe after the tee WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow these warnings could result in personal inju...

Page 5: ...d listed to ULC S636 3 Not all materials below may be approved or listed to ULC S636 4 Royal Pipe and IPEX are approved suppliers of ULC S636 pipe fittings cements and primers 5 Factory accessory conc...

Page 6: ...PLUG THESE PORTS A OPEN DOWNFLOW ORIENTATION B PLUG THESE PORTS A OPEN HORIZONTAL RIGHT ORIENTATION A OPEN B PLUG THESE PORTS HORIZONTAL LEFT ORIENTATION Representative drawing only some models may va...

Page 7: ...llations must comply with regulations of local building heating plumbing or other codes in effect in area where installation is made Complete the installation of the drainage system as follows 1 Dry f...

Page 8: ...te 7 Listen for gurgling noises in the venting and drainage systems This is an indication that there are dips in the piping system or that the traps are not operating properly Correct the conditions a...

Page 9: ...g doors and windows and all doors between the space in which the appliance s connected to the venting system are located and other spaces of the building 4 Close fireplace dampers 5 Turn on clothes dr...

Page 10: ...y in appearance H G SLOPE UP TO TERMINATION 1 4 IN PER FOOT Two inch pipe shown When another size pipe is used discard the 2 in tee in the kit and use a field supplied tee that is the same diameter as...

Page 11: ...ISTS G B A AIR FLOW H SLOPE UP TO TERMINATION 1 4 IN PER FOOT Two inch pipe shown When another size pipe is used discard the 2 in tee in the kit and use a field supplied tee that is the same diameter...

Page 12: ...PIPIING See NOTES in Figure 1 COMBUSTION AIR INLET PIPE MAY TERMINATE IN WELL VENTILATED CRAWL SPACE VENTILATED COMBUSTION AIR OR EXTERNAL TO STRUC TURE TRAP KIT MAY ALSO BE APPLIED SLOPE UP TO TERMIN...

Page 13: ...rnace L12F029 Fig 12 Combustion Air and Vent Pipe Diameter Transition Location and Elbow Configuration Representative drawing only some models may vary in appearance TO CODE APPROVED DRAIN OR CONDENSA...

Page 14: ...rrier Company Edition Date 04 20 Catalog No AG KGAET 06 Replaces AG KGBET 01 KGAET0201ETK Installation Instructions Manufacturer reserves the right to change at any time specifications and designs wit...

Reviews: