KGAET0201ETK: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

4

L12F021

Fig. 3 – Condensate Trap Plumbing Options for Combustion Air Pipe (ONLY) Above Furnace

INSTALLATION 

In  this  application,  ALL  vent  piping  MUST  be  sloped  toward  the

External Vent Trap Kit. The Internal Drain Trap Plug MUST be installed

in the vent/high-pressure side of the collector box trap connection in the

furnace (see 

Fig. 3

). The Trap Kit MUST be installed at the lowest point

in the venting system.

Example Trap Kit component installations are shown in 

Fig. 1

. Install as

shown in 

Fig. 3

 through 

Fig. 7

.

NOTE: 

NOTE:    This  kit  is  designed  for  use  with  2-in.  (50  mm)

PVC/ABS  DWV  vent/exhaust  pipe  applications.  Additional  pipe

diameters are usable when field-supplied PVC fittings are used with the

condensate trap supplied in kit (see 

Fig. 9

) for proper placement of pipe

diameter transitions. 

Representative drawing only, some models may vary in appearance

TO CODE--APPROVED DRAIN

OR CONDENSATE PUMP

COMBUSTION AIR

INLET PIPE

OPEN ’STAND PIPE’

FOR A/C OR HUMIDIFIER

DRAIN

OPEN ’STAND PIPE’

FOR A/C OR HUMIDIFIER

DRAIN

TO CODE--APPROVED DRAIN

OR CONDENSATE PUMP

COMBUSTION AIR

INLET PIPE

Two inch pipe
shown. When
another size
pipe is used,
discard the
2-in. tee in
the kit and
use a field
supplied tee
that is the
same
diameter as
the pipe
being used.

Two inch pipe

shown. When

another size pipe is

used, use the 2-in.

tee in the kit and

transition to the

pipe diameter

required in the

vertical portion of

the pipe after the

tee.

WARNING

!

CARBON MONOXIDE POISONING HAZARD

Failure  to  follow  these  warnings  could  result  in  personal  injury  or

death.

The Internal Drain Trap Plug MUST BE APPLIED to the vent side of

the  collector box  trap  connection  of  the  furnace  when the  trap  kit  is

applied to the vent/exhaust piping system. Failure to do this may result

in vent gasses being released into the living space.

Failure  to  use  a  properly  constructed  trap(s)  or  NOT  water-priming

trap(s) before operating furnace may allow positive pressure vent gases

to  enter  the  structure  through  drain  tube.  Vent  gases  contain  carbon

monoxide which is tasteless and odorless.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution could result in intermittent unit operation.
When the Internal Drain Trap Plug is used, the inducer housing may fill

with condensate if any of the vent piping that is external to the furnace

is sloped toward the furnace.

NOTICE

!

Drain  pipe  and  fittings  must  conform  to ANSI  standards  and ASTM

D1785 or D2846. CPVC or PVC cement and primer must conform to

ASTM D2564 or F493 (see 

Table 2

). See section for Special Venting

Requirements in the furnace installation instructions Venting section for

installations in Canada for pipe, fittings, cement, and primer material

requirements for Canadian installations.

WARNING

!

FIRE HAZARD

Failure to follow this warning could result in personal injury, death or

property damage. 

Solvent cements and primers are combustible. Keep away from heat,

sparks  and  open  flame.  Use  only  in  well-ventilated  areas.  Avoid

breathing in vapor or allowing contact with skin or eyes.

Summary of Contents for KGAET0201ETK

Page 1: ...r Follow the manufacturer s instructions in the use of primer and cement and never use primer or cement beyond its expiration date The safe operation as defined by ULC S636 of the vent system is based...

Page 2: ...rainage system and possibly the living space See Fig 3 Application to Combustion Air Inlet Piping Systems This Trap Kit may used to help prevent liquid moisture from the inlet piping system from enter...

Page 3: ...be either away from trap vent side or toward trap combustion air side curve of vent tee must be positioned toward termination toward major flow of condensate except as shown in Fig 2 i When larger di...

Page 4: ...t and transition to the pipe diameter required in the vertical portion of the pipe after the tee WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow these warnings could result in personal inju...

Page 5: ...d listed to ULC S636 3 Not all materials below may be approved or listed to ULC S636 4 Royal Pipe and IPEX are approved suppliers of ULC S636 pipe fittings cements and primers 5 Factory accessory conc...

Page 6: ...PLUG THESE PORTS A OPEN DOWNFLOW ORIENTATION B PLUG THESE PORTS A OPEN HORIZONTAL RIGHT ORIENTATION A OPEN B PLUG THESE PORTS HORIZONTAL LEFT ORIENTATION Representative drawing only some models may va...

Page 7: ...llations must comply with regulations of local building heating plumbing or other codes in effect in area where installation is made Complete the installation of the drainage system as follows 1 Dry f...

Page 8: ...te 7 Listen for gurgling noises in the venting and drainage systems This is an indication that there are dips in the piping system or that the traps are not operating properly Correct the conditions a...

Page 9: ...g doors and windows and all doors between the space in which the appliance s connected to the venting system are located and other spaces of the building 4 Close fireplace dampers 5 Turn on clothes dr...

Page 10: ...y in appearance H G SLOPE UP TO TERMINATION 1 4 IN PER FOOT Two inch pipe shown When another size pipe is used discard the 2 in tee in the kit and use a field supplied tee that is the same diameter as...

Page 11: ...ISTS G B A AIR FLOW H SLOPE UP TO TERMINATION 1 4 IN PER FOOT Two inch pipe shown When another size pipe is used discard the 2 in tee in the kit and use a field supplied tee that is the same diameter...

Page 12: ...PIPIING See NOTES in Figure 1 COMBUSTION AIR INLET PIPE MAY TERMINATE IN WELL VENTILATED CRAWL SPACE VENTILATED COMBUSTION AIR OR EXTERNAL TO STRUC TURE TRAP KIT MAY ALSO BE APPLIED SLOPE UP TO TERMIN...

Page 13: ...rnace L12F029 Fig 12 Combustion Air and Vent Pipe Diameter Transition Location and Elbow Configuration Representative drawing only some models may vary in appearance TO CODE APPROVED DRAIN OR CONDENSA...

Page 14: ...rrier Company Edition Date 04 20 Catalog No AG KGAET 06 Replaces AG KGBET 01 KGAET0201ETK Installation Instructions Manufacturer reserves the right to change at any time specifications and designs wit...

Reviews: