background image

SYSTXCCUIZ01-- V

Infinity

t

Control

Installation Instructions

HOLD

COOL

HEAT

OFF

ZONE

I

NFINITY

 

S

YSTEM

A04031

Fig. 1 -- Infinity

t

Zone Control

NOTE

: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION AND START--UP OVERVIEW

2

. . . . . . . . . .

INSTALLATION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLING INFINITY ZONE CONTROL

4

. . . . . . . . . . . . . .

INITIAL POWER--UP

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

QUICK START

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALL / SERVICE MENUS

9

. . . . . . . . . . . . . . . . . . . . . . . . .

EQUIPMENT SUMMARY MENU

9

. . . . . . . . . . . . . . . . . . . . . .

INSTALL MENU

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SETUP MENU

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CHECKOUT MENUS

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SERVICE MENUS

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

OPERATIONAL INFORMATION

16

. . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

19

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SYSTEM MALFUNCTION SCREEN

20

. . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury or property
damage. Consult a qualified installer, service agency or your

distributor or branch for information or assistance. The qualified

installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings and cautions

included in literature and attached to the unit. Consult local

building codes and the current edition of the National Electrical
Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical
Code CSA C22.1.

Recognize safety information. When you see this symbol

on

the unit and in instructions or manuals, be alert to the potential for
personal injury. Understand the signal words

DANGER

,

WARNING

, and

CAUTION

. These words are used with the

safety--alert symbol.

DANGER

identifies the most serious hazards,

which

will

result in severe personal injury or death.

WARNING

signifies hazards, which

could

result in personal injury or death.

CAUTION

is used to identify unsafe practices, which

may

result

in minor personal injury or product and property damage.

NOTE

is used to highlight suggestions which

will

result in enhanced

installation, reliability, or operation.

INTRODUCTION

The Infinity Zone System consists of several intelligent
communicating components which includes the Infinity Zone

Control (or User Interface), Smart Sensors, Damper Control
Module, variable speed furnace or FE fan coil, 2--stage AC or HP

and Infinity Packaged Products, which continually communicate

with each other via a four--wire connection called the ABCD bus.
Commands, operating conditions, and other data are passed

continually between components over the ABCD bus. The result is
a new level of comfort, versatility, and simplicity.
All Infinity furnaces or fan coils are variable--speed and

multi--stage for maximum flexibility, efficiency, and comfort. They
support controlled ventilation, humidification, dehumidification,

and air quality control. Either an Infinity (communicating) or a
standard 24VAC controlled outdoor unit may be used.
When using conventional outdoor units, the Infinity furnace or fan
coil provides the 24 volt signals needed to control them. Also, the

Infinity Damper Control Module (P/N SYSTXCC4ZC01) allows

connection of a Carrier HRV or ERV without the need for a
separate wall control.
All system components are controlled through the wall mounted
Infinity Zone Control, which replaces the conventional thermostat

and provides the homeowner with a single wall control for all

features of the system.

Summary of Contents for Infinity SYSTXCCUIZ01-B

Page 1: ...for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe pers...

Page 2: ...ne Control and Room Sensors should NOT be mounted S Close to a window on an outside wall or next to a door leading to the outside S Exposed to direct light or heat from a lamp sun fireplace or other t...

Page 3: ...ces shown in Fig 3 through 10 The User Interface will snap together with either the Recess Mount or the Surface Mount backplate Recess Mount This provides the thinnest mounting configuration See Fig 4...

Page 4: ...ative Backplate Recessed Mount Interlocking Tabs 4 Recessed terminal block in wall 11 2 38 1 mm wide by 21 8 54 mm high A07150 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlockin...

Page 5: ...e dampers humidifier ventilator UV lights etc 12 Turn on power to equipment See wiring diagrams Fig 11 12 and 13 for connecting the Infinity Zone Control and Smart Sensors to the Damper Control Modul...

Page 6: ...speed indoor equipment furnace or fan coil cannot be found the User Interface will display CANNOT COMMUNICATE WITH INDOOR UNIT This MUST be corrected before the initial power up sequence can continue...

Page 7: ...hen press right side button to continue UV Lights Installed This screen will appear to select whether UV lights are installed on the system select YES or NO then press right side button to continue Zo...

Page 8: ...LEFT Up Down button 3 Press SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setti...

Page 9: ...IES SYSTEM MAINTENANCE BACK SELECT A04089 Fig 27 Setup Menu Setup Thermostat Auto Mode Setup S Enable Disable Auto Changeover mode default Enable S Auto Changeover Time may be adjusted 5 to 120 minute...

Page 10: ...ehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor unit is used S MAXIMUM 400 CFM ton Dehum Airflow S NORMAL factory default When equipment is running t...

Page 11: ...ry if a 2 stage outdoor unit is used S EFF 350 fixed airflow used to achieve specified ratings no dehumidification airflow reduction This is nominally 350 CFM ton but will vary if a 2 stage outdoor un...

Page 12: ...ff default Turns on Quiet Shift function in 1 stage or 2 stage communicating heat pumps High Cool Latch S OFF default S ON high cool stage on at all times unzoned only S 80 to 110_F 27 to 43_C unzoned...

Page 13: ...F DEFROST W WATER YES BLOWER OFF DELAY 30 SEC BACK A07031 Fig 31 Hydronic Heat Setup HOT WATER LOCKOUT Outside temperature above which the hot water will not operate except for defrost if selected S...

Page 14: ...ange to FURNACE CHECK and show the current operating status of the furnace Checkout Electric Heat S ELECTRIC HEAT RUNTIME 5 min Default time 5 min Range 0 120 min If you have a fan coil with electric...

Page 15: ...ximum amount of airflow to each zone Select ZONE then select AIRFLOW LIMIT When Start is pressed right side button the selected zone s damper will fully open all others will close and the indoor unit...

Page 16: ...tioner FN Furnace FC Fan Coil ZN1 Zone Board 1 ZN2 Zone Board 2 SPP Packaged product SAM System Access Module Service Run Fault History This information is stored in the equipment circuit boards if co...

Page 17: ...elected recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time It operates in both heating and cooling This only applies to programmable...

Page 18: ...ed to overcool the space up to 3_F 6_C if the humidity level is above the cooling humidity target setpoint The amount of over cooling allowed varies with the dehumidification demand the cooling demand...

Page 19: ...e run mode How do I get back to start up 1 Press the ADVANCED button for at least 10 seconds 2 Install Service menu will appear 3 Scroll down to the INSTALL selection 4 Press the right side button the...

Page 20: ...mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing the V model user interface...

Reviews: