SYSTXCCUID01-- V

Infinity

t

Control

Installation Instructions

HOLD

COOL

HEAT

OFF

ZONE

I

NFINITY

 

S

YSTEM

A04031

Fig. 1 -- Infinity

t

Control

NOTE

: Read the entire instruction manual before starting the

installation.

US Patents: Carrier

r

U.S. Pat No. 7,243,004, Carrier

r

U.S. Pat No. 7,775,452

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION AND START--UP OVERVIEW

2

. . . . . . . . . .

INSTALLATION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLING INFINITY CONTROL

3

. . . . . . . . . . . . . . . . . . . .

INITIAL POWER--UP

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

QUICK START

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALL / SERVICE MENUS

8

. . . . . . . . . . . . . . . . . . . . . . . . .

EQUIPMENT SUMMARY MENU

8

. . . . . . . . . . . . . . . . . . . . . .

INSTALL MENU

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SETUP MENU

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CHECKOUT MENUS

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SERVICE MENUS

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

OPERATIONAL INFORMATION

15

. . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SYSTEM MALFUNCTION SCREEN

18

. . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury or property
damage. Consult a qualified installer, service agency or your

distributor or branch for information or assistance. The qualified

installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings and cautions

included in literature and attached to the unit. Consult local

building codes and the current edition of the National Electrical
Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical
Code CSA C22.1.

Recognize safety information. When you see this symbol

on

the unit and in instructions or manuals, be alert to the potential for
personal injury. Understand the signal words

DANGER

,

WARNING

, and

CAUTION

. These words are used with the

safety--alert symbol.

DANGER

identifies the most serious hazards,

which

will

result in severe personal injury or death.

WARNING

signifies hazards, which

could

result in personal injury or death.

CAUTION

is used to identify unsafe practices, which

may

result

in minor personal injury or product and property damage.

NOTE

is used to highlight suggestions which

will

result in enhanced

installation, reliability, or operation.

INTRODUCTION

The Infinity System consists of several intelligent communicating
components which includes the Infinity Control (or User

Interface), variable speed furnace or FE fan coil, 2--stage AC or HP
and Infinity Packaged Products, which continually communicate

with each other via a four--wire connection called the ABCD bus.

Commands, operating conditions, and other data are passed
continually between components over the ABCD bus. The result is

a new level of comfort, versatility, and simplicity.
All Infinity furnaces or fan coils are variable--speed and multi stage

for maximum flexibility, efficiency, and comfort. They support

controlled ventilation, humidification, dehumidification, and air
quality control. Either an Infinity (communicating), or a standard

24VAC controlled outdoor unit may be used.
When using conventional outdoor units, the Infinity furnace or fan

coil provides the 24 volt signals needed to control them. Also, the
Infinity Network Interface Module (P/N SYSTXCCNIM01) allows

connection of a Carrier HRV or ERV without the need for a

separate wall control.
All system components are controlled through the wall mounted

Infinity Control, which replaces the conventional thermostat and
provides the homeowner with a single wall control for all features

of the system.

Summary of Contents for Infinity SYSTXCCUID01-V

Page 1: ...in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the...

Page 2: ...red to the terminal block connectors labeled S1 and S2 at the User Interface backplate or the ZS1 and ZS1C connection at the Damper Control Module In either case the Infinity Control will automaticall...

Page 3: ...ecorative Backplate Recessed terminal block in wall 11 2 wide by 2 1 8 high Recessed Mount Interlocking Tabs 4 A03190 Fig 7 Recessed Mount Assembly Surface Mount Backplate to wall Interlocking Tabs 4...

Page 4: ...insulation from each wire 8 Match and connect thermostat wires to proper terminals on User Interface backplate See wiring diagram Fig 11 12 and 13 A B C D A B C D User Interface Green Yellow White Re...

Page 5: ...o energize upon a switch or contact closure For this application a 24VAC N O Isolation Relay DPST MUST be used to prevent mixing the internal humidifier power with the indoor equipment transformer App...

Page 6: ...asterisks will appear next to electric heater sizes that may cause excessive airflow ELECTRIC HEATER NOT IDENTIFIED ENTER SIZE 5 KW NONE 5 10 15 KW PRESS TO MAKE SELECTION BACK CONTINUE A03197 Fig 18...

Page 7: ...SCROLL button down to highlight MINUTE 4 Adjust the MINUTE setting using the LEFT Up Down button 5 Press SCROLL button down to highlight DAY 6 Adjust the current DAY setting using the LEFT Up Down but...

Page 8: ...i e DIP switches on a furnace All configuration settings made effective from this menu will override equipment configuration made by dip switches Fig 25 shows all the information that can be found in...

Page 9: ...tion enables the full dehumidify and comfort capabilities of the system When COMFORT is not selected the unit will not run reduced airflows for dehumidification S EFF 325 fixed airflow used to achieve...

Page 10: ...1 10000 This setting will adjust the furnace s airflow to compensate for altitude Altitude adjustment is not available with older furnaces Please see furnace instructions for further details Setup Fan...

Page 11: ...ling Lockout set to NONE Low ambient kits are not needed with communicating outdoor units For detailed sequence of operation see outdoor unit installation instructions Entered Size S dependent on indo...

Page 12: ...ble range from OFF 500 CFM minimum to 400 CFM ton cooling maximum in 50 CFM increments S Default is the cooling airflow 350 CFM ton S OFF selection does not turn off airflow if heat pump is defrosting...

Page 13: ...eat Enter the run time in minutes of each stage of heat to be exercised then press START right side button The display will change to show the fan coil s operating status Checkout Heat Pump Heating S...

Page 14: ...ic pressure that the fan coil is currently experiencing S If static pressure cannot be accurately calculated the display will read UNKNOWN When this is seen the system is adjusting to high static pres...

Page 15: ...is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan...

Page 16: ...lowed with greater dehumidification demand When the space temperature is at or above 75_F 24_C and the dehumidify demand is high over cooling up to 3_F 2_C is allowed As the space temperature approach...

Page 17: ...ctly to indoor unit with a short piece of thermostat wire Add other devices one at a time to determine where the communication issue exists Display says Outdoor Unit Not Found and I have a two stage c...

Page 18: ...controller While in service mode the V model user interface will not transfer any settings or information to or from the regular user interface it only takes over control of the system After removing...