background image

If Fan Switch on 4 zone controller is set to ON instead of Auto,
then system fan will run continuously. Any time Comfort Zone is
operating fan, it will be in active control of system.

NOTE:

If Auto Fan Off For Heating option (rotary switch

position T-9) is ON, and Fan Switch on the 4 zone controller is
ON, Comfort Zone will operate fan full time.

Operating fan continuously will place Comfort Zone in a Float
Mode 
any time no active heating or cooling is taking place. During
Float Mode, Comfort Zone will position zone dampers based upon
demand in each zone. Comfort Zone will check air temperature in
duct work and allow air into zones if it will help zones reduce their
individual demands. For example, if temperature of air in duct
work is 65°F, cooling comfort setpoint for a zone is 72°F, and
space temperature is 73°F, then Comfort Zone will open damper
servicing that zone and allow cooler air into space.

Ventilation Mode is only in effect when temperature of supply air
is between 65°F and 80°F. Ventilation Mode establishes minimum
position of zone dampers and is intended to help air movement
throughout zones and reduce chance of having areas which are
stagnant or have high humidities with respect to rest of system.
The changes to dampers are detailed in the next section "Control-
ling the Zone Dampers."

CONTROLLING THE ZONE DAMPERS

The zone dampers have a total of 16 possible positions or
increments which are numbered 0 (zero) through 15. Position
number 0 is fully closed and position number 15 is fully open.
While damper servicing reference zone remains fully open, all
other zone dampers are positioned by selecting a position equal to
demand of space in tenths of a degree. (See Table 2.)

For example, a zone which has a 1.0°F demand will have damper
set to position number 10 while a zone which has a demand of
0.5°F will have damper set to position number 5. A demand of 0
(zero) will fully close zone damper. Any zone which has a demand
greater than 1.5°F will remain fully open.

Notice that positions are based upon tenths of a degree Fahrenheit.
If Comfort Zone has Celsius Temperature Display option (rotary
position T-2) turned on, the damper control is still based upon
Fahrenheit scale.

The damper positions in table are also used during a Float Mode.
A zone with a demand of 0.5°F will be set to position number 5.

The actual control of zone dampers by Comfort Zone system can
be modified using 3 configurable options. These are Maximum
Damper Position, Minimum Damper Position, and Ventilation
Mode.

These options apply to all zone dampers simultaneously. Any
dampers servicing Zone 1 cannot be configured differently than
those servicing Zone 2. The options are as follows:

1. The Maximum Damper Position (rotary position number

S-4) sets maximum open damper position for all 4 zones. The
allowable range for this option is damper positions number 8
through number 15 (fully open). The factory default is 15. The
only time zone dampers will exceed this position is if system
fan is off or zone dampers are being calibrated.

2. The Minimum Damper Position (rotary position number

S-5) sets minimum open damper position for all 4 zones. The
allowable range for this option is damper positions number 0
through number 7. The factory default is number 0 (fully
closed). If Ventilation Mode (rotary position T-25) is turned
OFF, then minimum damper position will be an absolute
minimum regardless of operating mode. If Ventilation Mode
is turned ON, then minimum damper position will be mini-
mum position during a Ventilation Mode only and dampers
will be allowed to fully close at any other time.

3. Ventilation Mode (rotary position T-25). If Ventilation Mode

is turned ON, then any time air inside supply air duct work is
between 65°F and 80°F, system will be in a "Ventilation
Mode". During a Ventilation Mode all zone dampers will have
a minimum position which is set by Minimum Damper
Position (rotary position S-5). The zone dampers are not
allowed to fully close as long as supply air temperature
remains within the 65°F-80°F range. If supply air temperature
falls outside the 65°F-80°F range, then zone dampers may
fully close.

NOTE:

If Ventilation Mode option (rotary position T-25) is

turned ON, and Minimum Damper Position (rotary position S-5) is
set to position 0, there is no difference between Float Mode and
Ventilation Mode. 
In other words, Ventilation Mode option has
no effect on system.

OPERATING THE HEATING AND COOLING EQUIPMENT

Before any heating or cooling equipment is started, Comfort Zone
must first choose between heating or cooling. For most of the year
there is little question as to the need for heat or cooling. But for
portions of the year, particularly during mid-season, a building
may have simultaneous needs for both heating and cooling.

The first step in selecting heating or cooling is the determination of
a Reference Zone. If there is a single zone which has greatest
demand, then it will become the Reference Zone and Comfort
Zone will start equipment based upon needs of that zone. If 2 zones
have same "greatest demand" but in different modes (1 needs
heating and the other needs cooling), then Comfort Zone will
select mode which has greatest number of zones which require
same mode.

CONTROL STRATEGY FOR HEATING / COOLING STAGES

The Comfort Zone system will attempt to minimize use of
additional stages of heating or cooling equipment. In an ideal case,
building conditioning needs can be supplied by first stage cooling
or first stage heating alone.

For most heat pump applications, there may be only 2 or 3 stages
of heat depending upon type of emergency heater present. For a
heat pump, secondary heat source will generally be an electric strip

Table 2—Zone Damper Positions

Damper Position Versus Zone Demand

DAMPER

POSITION

DEMAND °F

DEMAND °C

0

Fully Closed

0

0

1

0.1

0.06

2

0.2

0.11

3

0.3

0.17

4

0.4

0.22

5

0.5

0.28

6

0.6

0.33

7

0.7

0.39

8

0.8

0.44

9

0.9

0.50

10

1.0

0.55

11

1.1

0.61

12

1.2

0.67

13

1.3

0.72

14

1.4

0.78

15

Fully Opened

1.5

0.83

9

Summary of Contents for COMFORT ZONE ZONEKIT4ZCAR

Page 1: ...r Table 21 Wiring Diagrams 22 31 Configuration Table 32 SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause fire electrical shock or other conditions...

Page 2: ...to COM BUS a 3 wire cable must be separate from the 5 wire cable The thermostats should be located approximately 5 ft above floor and must be located within 200 ft of Comfort Zone Center SHIELDED CABL...

Page 3: ...Level back plate and tighten screws Step 4 Install Zone Dampers IMPORTANT If conditions exist for possible condensing motor must be positioned for adequate draining See Fig 6 NOTE If a multi damper en...

Page 4: ...All zone dampers and duct work must be properly supported according to local codes or SMACNA standards RECTANGULAR METAL DUCT WORK 1 Make connections using S lock and drives See Fig 10 2 Properly seal...

Page 5: ...Installation Instructions packaged with barometric bypass Failure to properly install bypass damper can cause perma nent damage to the HVAC equipment For single speed furnace applications bypass air m...

Page 6: ...ensor on room sensors Do not locate on an outside wall or next to a return air grill 1 Separate the 2 parts of sensor and mount back plate with provided flat head screw 2 Pull a 2 wire conductor throu...

Page 7: ...HEAT 1 W1 HEAT 2 W2 FAN G RV COOL 0 OR RV HEAT B Power CHR 06 Communication Bus COMFORT ZONE I O R G W R G COMM BUS CONTROLLER COMM BUS HAM R W R W R W R W R W R W OAT LAT ZT4 ZT3 ZT2 SHIELD GROUND W...

Page 8: ...TION OF A REFERENCE ZONE IN THE SYSTEM The first step in any heating or cooling cycle requires Comfort Zone to evaluate zones determine if heating or cooling is needed and select a Reference Zone The...

Page 9: ...open The factory default is 15 The only time zone dampers will exceed this position is if system fan is off or zone dampers are being calibrated 2 The Minimum Damper Position rotary position number S...

Page 10: ...4 are shown in Table 4 Under no circumstances may the W1 and Y1 contacts on the relay pack be jumpered together This is a common practice for many heat pump installations but will cause improper opera...

Page 11: ...y may vary widely For residen tial application the need for System Mode Reselect is normally not frequent unless the building has unusual architectural features or problems with HVAC system High Low T...

Page 12: ...the value of setting Press the COOL up or down setpoint buttons to change setting number and the HEAT up or down setpoint buttons to change value Refer to Table 6 for settings and their definitions 1...

Page 13: ...L up or down setpoint buttons to change toggle number and the HEAT up or down setpoint buttons to change status of toggle See Table 11 Step 12 Wiring Diagrams Refer to Tables 7 and 8 for wiring diagra...

Page 14: ...one at different times during the day and week See Fig 18 to become familiar with various parts of the 4 zone controller SYSTEM SWITCHES System switches select desired equipment operation Heat Switch...

Page 15: ...ay whenever system is in this mode Set vacation mode setpoints Setting The Clock The clock display will normally show hour minutes AM or PM and day 1 Set minutes Press SELECT MIN HR DAY button once Pr...

Page 16: ...eature can verify that each zone damper is operating properly by manually opening and closing each zone When rotary switch dial is moved onto another position Damper Service Mode will be cleared and c...

Page 17: ...omfort Zone con troller detects and replaces faulty data contained within its memory with factory selected default values Transparent Errors Occur when Comfort Zone controller de tects a system or zon...

Page 18: ...e and set points for zone 2 via the 3 wire communication bus at 1 ad dress below controller The system reads zone 2 temperature via the remote room sensor OFF T14 Smart Sensor Attached For Zone 3 The...

Page 19: ...LEDs on the CHR06 relay pack are indicating the correct relay is closed If not check for a bad relay 2 Measure voltage across common red and any de energized relay Voltage should be 24 vac 3 Apply 24...

Page 20: ...2 Configuration Error 1 Turn selection dial to position T2 T11 T12 T18 T20 T22 and T24 2 Check and correct the configuration 3 Return selection dial to any run mode position 13 Configuration Error 1 T...

Page 21: ...ed or open 1 Check wiring and sensor 2 Replace failed sensor if necessary Valid temperature range 30 180 F 47 Bus Access Error Controller can not communicate on bus 1 Check 3 wire bus between controll...

Page 22: ...296 UNIT 24 VAC R C 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFORT ZONE CENTER G W2 E...

Page 23: ...itioner Continued A94034 E UNIT 24 VAC R 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFO...

Page 24: ...ONER Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FURNACE COMFORT ZONE CENTER W2 R C C Y Y2 W W1 G NOTE Locking furnace into low...

Page 25: ...TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FURNACE COMFORT ZONE CENTER G Y2 H R1 R R1 Relay DPST Pilot Duty 24 v coil HN61KK...

Page 26: ...one Center to W2 on the furnace control board UNIT 24 VAC R C R Y1 L 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O...

Page 27: ...T ZONE SYSTEM G C R Y W2 O W2 R C L B W3 E O Y1 Y Y2 A93243 UNIT 24 VAC R C 2 SPEED HEAT PUMP 38YD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL...

Page 28: ...mp Continued UNIT 24 VAC R 2 SPEED HEAT PUMP 38YD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFORT ZONE SYSTEM G C R...

Page 29: ...N position up when using Two Stage Relay Kit KGATT0101VSP Accessory Optional A93298 UNIT 24 VAC R Y W2 STANDARD SINGLE SPEED HEAT PUMP Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y...

Page 30: ...OOL O RV HEAT O OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER G Y1 R1 R R1 Relay DPST Pilot Duty 24 v coil HN61KK324 or Equivalent C F W2 O W Y RELAY COIL G r e e n P5 CONNECTION AT CONTROL BOARD Blac...

Page 31: ...Configure the 4 Zone controller to act as if it were controlling a single speed heat pump Turn T 6 ON Turn T 9 T 26 OFF Set S 7 to 0 Let the 38YD perform the dual fuel optimization R W2 O W2 R G C W3...

Page 32: ...Hz Operation OFF T25 Ventilation Mode OFF T26 Two Stage Heat Pump OFF T27 Dx Sensor For LAT Checking OFF T28 Cool Without Fan OFF SETTING S 1 4 Zone Controller Bus Address 04 S 2 Max Cooling Setpoint...

Reviews: