background image

heater. The electric strip heat is much more expensive to operate
when comparing cost per unit of heat. Because auxiliary stages of
heating tend to be more expensive to operate, Comfort Zone
attempts to keep number of stages at a minimum.

CONFIGURATION OPTIONS FOR EQUIPMENT
OPERATION

Comfort Zone has several configurable options which allow it to
control different types of HVAC equipment and change the
manner in which the equipment is controlled. This first group must
be set given the type of HVAC equipment installed. These include:

1. Heat Pump Operation (Rotary Position T-6).

2. Two-Stage Heat Pump (Rotary Position T-26).

3. Dual Fuel trip temperature (Rotary Position S-7).

4. Auto Fan Off For Heat (Rotary Position T-9).

The second group modifies the way the HVAC equipment is
controlled. These include:

1. Comfort Trend Staging (Rotary Position T-8).

2. System Mode Reselect (Rotary Position T-22).

3. High/Low Temperature Limits Enabled (Rotary Position

T-10).

4. High Temperature Trip Limit (Rotary Position S-6).

5. Dx Sensor (Rotary Position T-27).

6. Smart Start (Heat Pump Strip Heat Economy Feature)

The first options which must be set are based upon the type heater
or heaters used. These are shown in Table 3. The only option
which appears to impact cooling operation is Two-Stage Heat
Pump which implies the availability of 2 stages of cooling. In
reality there are no changes to cooling control scheme.

Comfort Zone assumes that there are always 2 stages of cooling
present. These are connected to the Comfort Zone Relay Pack on
the Y1 and Y2 contacts.

RELAY PACK TO HVAC EQUIPMENT CONNECTIONS

Given system configuration, Comfort Zone can determine number
of heating stages that it will actually control and which relay
outputs will be used to control each stage of heat. Comfort Zone
can control up to 4 stages of heat depending upon system
configuration.

For cooling only applications with any type of heater, Comfort
Zone will only control 2 stages of heat. If system uses a heat pump,
then Comfort Zone will control 3 stages of heat. The additional
stage is heat pump compressor contact. The auxiliary heat is still
2 stages. If system uses a 2 stage heat pump, then Comfort Zone
will control 4 stages of heat, 2 stages for heat pump and 2 stages
for auxiliary heat.

The Comfort Zone Relay Pack outputs are shown in Table 4. The
Y1 and Y2 contacts are used for compressor contacts only.
Comfort Zone operates heat pumps by energizing compressor
contacts and controlling reversing valve through Reversing Valve
(RV) relay output. The W1 and W2 contacts are always used for
heat sources. These are heating only units such as furnaces, strip
heaters, etc. The relay outputs for Comfort Zone 1.4 are shown in
Table 4.

Under no circumstances may the W1 and Y1 contacts on the
relay pack be jumpered together. This is a common practice
for many heat pump installations but will cause improper
operation of the Comfort Zone (1.4 or greater) system.

STARTING THE HVAC EQUIPMENT

Once Comfort Zone selects a mode, controller will use configu-
ration options to modify control of HVAC equipment. The
controller first selects number of stages of heating and cooling that
may be applied to building load. The "available" stages are
determined by Reference Zone temperature demand and are shown
in Table 5.

Using Table 5, if Reference Zone has a 2.3°F demand, then
Comfort Zone may use 2 stages of cooling or 2 stages of heating.
The HVAC equipment may not have 3 stages of heat or even 2
stages of cooling. The table is only used to determine what
equipment Comfort Zone is allowed to turn on at any given time
during a heating or cooling cycle. Actual operation of stages
depends on other variables as well.

Normally Comfort Zone will start equipment operation when it has
a demand of 1.5°F or greater. In some cases, Comfort Zone will be
facing a demand greater than 1.5°F when a mode is starting. This
can occur when user changes setpoints in a zone or if a schedule
change has reset the Comfort Setpoints.

Table 3—Heating System Option Vs. Type of Heater Used

HEATER TYPE USED

IN SYSTEM

HEAT PUMP

SYSTEM TOGGLE:

T-6

TWO STAGE

HEAT PUMP

TOGGLE: T-26

DUAL FUEL

SYSTEM SWITCH:

S-7

FAN ON

FOR COOLING ONLY

TOGGLE:

T-9

Single-Stage Heat Pump

On

Off

0

o

F (off)

Off

Two-Stage Heat Pump

On

On

0

o

F (off)

Off

Heat Pump/Furnace Dual

Fuel

On

Off

10 to 60

o

F

Off

Two-Stage Heat Pump,

Furnace Dual Fuel*

On

On

0°F

Off

Furnace Heat Only

Off

Off

0

o

F (off)

On or Off

Strip Heater Only

Off

Off

0

o

F (off)

Off

* Refer to 2-speed heat pump Installation and Start-Up Instructions for details regarding 2-speed heat pump operation. It is recommended that heat pump control board
controls operation of this equipment and not Comfort Zone.

Table 4—Available Heating and Cooling Stages Vs. System Type

TYPE OF HVAC

EQUIPMENT USED

COOLING STAGE 1

COOLING STAGE 2

HEAT STAGE 1

HEAT STAGE 2

HEAT STAGE 3

HEAT STAGE 4

Cooling Only, any Heater Type

Y1

Y2

W1

W2

--

--

Single-Stage Heat Pump

Y1

--

Y1

W1

W2

--

Two-Stage Heat Pump

Y1

Y2

Y1

Y2

W1

W2

For cooling applications, the second stage of an air conditioner is not necessarily more expensive to operate than first stage. But additional cooling can drive down the
efficiency of a 2-speed air conditioner and longer use of first stage alone tends to deliver better humidity control in moist climates. Again, because of these advantages,
Comfort Zone will attempt to minimize use of second stage cooling. This is not as great of a concern for a heating application, because the majority of small air
conditioning systems sold today (5 tons and below) are single-stage cooling only.

10

Summary of Contents for COMFORT ZONE ZONEKIT4ZCAR

Page 1: ...r Table 21 Wiring Diagrams 22 31 Configuration Table 32 SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause fire electrical shock or other conditions...

Page 2: ...to COM BUS a 3 wire cable must be separate from the 5 wire cable The thermostats should be located approximately 5 ft above floor and must be located within 200 ft of Comfort Zone Center SHIELDED CABL...

Page 3: ...Level back plate and tighten screws Step 4 Install Zone Dampers IMPORTANT If conditions exist for possible condensing motor must be positioned for adequate draining See Fig 6 NOTE If a multi damper en...

Page 4: ...All zone dampers and duct work must be properly supported according to local codes or SMACNA standards RECTANGULAR METAL DUCT WORK 1 Make connections using S lock and drives See Fig 10 2 Properly seal...

Page 5: ...Installation Instructions packaged with barometric bypass Failure to properly install bypass damper can cause perma nent damage to the HVAC equipment For single speed furnace applications bypass air m...

Page 6: ...ensor on room sensors Do not locate on an outside wall or next to a return air grill 1 Separate the 2 parts of sensor and mount back plate with provided flat head screw 2 Pull a 2 wire conductor throu...

Page 7: ...HEAT 1 W1 HEAT 2 W2 FAN G RV COOL 0 OR RV HEAT B Power CHR 06 Communication Bus COMFORT ZONE I O R G W R G COMM BUS CONTROLLER COMM BUS HAM R W R W R W R W R W R W OAT LAT ZT4 ZT3 ZT2 SHIELD GROUND W...

Page 8: ...TION OF A REFERENCE ZONE IN THE SYSTEM The first step in any heating or cooling cycle requires Comfort Zone to evaluate zones determine if heating or cooling is needed and select a Reference Zone The...

Page 9: ...open The factory default is 15 The only time zone dampers will exceed this position is if system fan is off or zone dampers are being calibrated 2 The Minimum Damper Position rotary position number S...

Page 10: ...4 are shown in Table 4 Under no circumstances may the W1 and Y1 contacts on the relay pack be jumpered together This is a common practice for many heat pump installations but will cause improper opera...

Page 11: ...y may vary widely For residen tial application the need for System Mode Reselect is normally not frequent unless the building has unusual architectural features or problems with HVAC system High Low T...

Page 12: ...the value of setting Press the COOL up or down setpoint buttons to change setting number and the HEAT up or down setpoint buttons to change value Refer to Table 6 for settings and their definitions 1...

Page 13: ...L up or down setpoint buttons to change toggle number and the HEAT up or down setpoint buttons to change status of toggle See Table 11 Step 12 Wiring Diagrams Refer to Tables 7 and 8 for wiring diagra...

Page 14: ...one at different times during the day and week See Fig 18 to become familiar with various parts of the 4 zone controller SYSTEM SWITCHES System switches select desired equipment operation Heat Switch...

Page 15: ...ay whenever system is in this mode Set vacation mode setpoints Setting The Clock The clock display will normally show hour minutes AM or PM and day 1 Set minutes Press SELECT MIN HR DAY button once Pr...

Page 16: ...eature can verify that each zone damper is operating properly by manually opening and closing each zone When rotary switch dial is moved onto another position Damper Service Mode will be cleared and c...

Page 17: ...omfort Zone con troller detects and replaces faulty data contained within its memory with factory selected default values Transparent Errors Occur when Comfort Zone controller de tects a system or zon...

Page 18: ...e and set points for zone 2 via the 3 wire communication bus at 1 ad dress below controller The system reads zone 2 temperature via the remote room sensor OFF T14 Smart Sensor Attached For Zone 3 The...

Page 19: ...LEDs on the CHR06 relay pack are indicating the correct relay is closed If not check for a bad relay 2 Measure voltage across common red and any de energized relay Voltage should be 24 vac 3 Apply 24...

Page 20: ...2 Configuration Error 1 Turn selection dial to position T2 T11 T12 T18 T20 T22 and T24 2 Check and correct the configuration 3 Return selection dial to any run mode position 13 Configuration Error 1 T...

Page 21: ...ed or open 1 Check wiring and sensor 2 Replace failed sensor if necessary Valid temperature range 30 180 F 47 Bus Access Error Controller can not communicate on bus 1 Check 3 wire bus between controll...

Page 22: ...296 UNIT 24 VAC R C 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFORT ZONE CENTER G W2 E...

Page 23: ...itioner Continued A94034 E UNIT 24 VAC R 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFO...

Page 24: ...ONER Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FURNACE COMFORT ZONE CENTER W2 R C C Y Y2 W W1 G NOTE Locking furnace into low...

Page 25: ...TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FURNACE COMFORT ZONE CENTER G Y2 H R1 R R1 Relay DPST Pilot Duty 24 v coil HN61KK...

Page 26: ...one Center to W2 on the furnace control board UNIT 24 VAC R C R Y1 L 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O...

Page 27: ...T ZONE SYSTEM G C R Y W2 O W2 R C L B W3 E O Y1 Y Y2 A93243 UNIT 24 VAC R C 2 SPEED HEAT PUMP 38YD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL...

Page 28: ...mp Continued UNIT 24 VAC R 2 SPEED HEAT PUMP 38YD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFORT ZONE SYSTEM G C R...

Page 29: ...N position up when using Two Stage Relay Kit KGATT0101VSP Accessory Optional A93298 UNIT 24 VAC R Y W2 STANDARD SINGLE SPEED HEAT PUMP Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y...

Page 30: ...OOL O RV HEAT O OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER G Y1 R1 R R1 Relay DPST Pilot Duty 24 v coil HN61KK324 or Equivalent C F W2 O W Y RELAY COIL G r e e n P5 CONNECTION AT CONTROL BOARD Blac...

Page 31: ...Configure the 4 Zone controller to act as if it were controlling a single speed heat pump Turn T 6 ON Turn T 9 T 26 OFF Set S 7 to 0 Let the 38YD perform the dual fuel optimization R W2 O W2 R G C W3...

Page 32: ...Hz Operation OFF T25 Ventilation Mode OFF T26 Two Stage Heat Pump OFF T27 Dx Sensor For LAT Checking OFF T28 Cool Without Fan OFF SETTING S 1 4 Zone Controller Bus Address 04 S 2 Max Cooling Setpoint...

Reviews: