background image

2. Use vibration isolators (flex connectors) on zone dampers and

duct work to minimize noise.

3. Place dampers away from areas that may be noise sensitive.

4. TXV is required in air conditioning and heat pump applica-

tions.

5. Use separate isolated transformer to supply power to Comfort

Zone System (50 va minimum, class 2, field supplied).

6. Load calculations must be performed to determine equipment

size. Equipment selection is matched to block load. It is
imperative equipment is not oversized.

7. Duct work must be designed based off the sum of peaks plus

25 percent oversize. It is imperative duct work is not under-
sized.

INTRODUCTION

This installation guide pertains to revision 1.6 or greater. The
Comfort Zone System allows air conditioning and heating equip-
ment to control temperatures in up to 4 distinct spaces or Zones
within a building. Each zone has independent temperature settings.
The comfort temperature settings can change automatically
through the use of schedules. This allows Comfort Zone to change
temperature settings in zones to reflect occupancy or usage. For
example, you can condition the bedrooms in a home from 5:00 PM
through 7:00 AM or the kitchen from 3:00 PM through 6:00 PM.
The Comfort Zone System uses motorized air volume control
dampers (also called zone dampers) to regulate flow of condi-
tioned air into zones. In this manner Comfort Zone can selectively
heat or cool certain portions of a building depending upon space
temperature requirements.

INSTALLATION

Step 1—Check Equipment and Jobsite

INSPECT EQUIPMENT — File claim with shipping company,
prior to installation, if shipment is damaged or incomplete.

Step 2—Wiring

To prevent personal injury or possible equipment damage
disconnect power supply before routing wire.

All wiring must comply with local and state codes.

NOTE:

A remote room sensor requires a 2-wire cable, however,

it is recommended that a 5-wire cable be installed to allow for a
possible smart sensor upgrade. Connect white wire to terminal
labeled B- if a 5-wire cable is used. Connect red wire to R+.
Shielded cable is recommended to reduce noise interference.

NOTE:

Use No. 22 AWG color-coded, insulated (35°C min)

wire. If thermostats are to be located more than 100 ft from
Comfort Zone Center as measured along control voltage wires, use
18 AWG colored-coded wires to avoid excessive voltage drop.

All wiring is run back to Comfort Zone Center. Keep wires a
minimum of 12 in. from any AC voltage. Do not tie-wrap wires
together. When wiring to COM BUS, a 3-wire cable must be
separate from the 5-wire cable. The thermostats should be located
approximately 5 ft above floor and must be located within 200 ft
of Comfort Zone Center.

SHIELDED CABLE

General

1. All wiring should be shielded (except damper wiring) with 18

or 22 gage. The 3-wire, 5-wire, and Remote Sensor wire must
be in separate jacketed cable.

2. All system wiring must be within 1 building. Never connect

devices between 2 or more buildings.

Shielding For A Single Comfort Zone System

1. Fig. 16 Shows a Comfort Zone System with all possible

options. The shield from all devices should be tied together at
I/O board and terminated at shield ground at lower right hand
corner of board. Be sure shielding does not touch any other
wiring on board.

NOTE:

Do not connect shield wire at device end. Cut end and

tape up to avoid shorting.

Shielding For Multiple Comfort Zone Systems

1. If more than 1 Comfort Zone System resides on 1 job, they

may be tied together for communication purposes. If no
communication is required, then Comfort Zone System should
be wired separate and shielded as previously stated.

2. When 2 to 4 systems are on 1 job and require communication,

they should be daisy chained together through 3-wire commu-
nication bus at COM BUS HAM terminal.The shielding
should only be grounded at 1 point on end of communication
bus as shown in Fig. 2.

3. If more than 4 systems are used on 1 job, multiple device

buses must be used. Each device bus must be separated by an
ISOSAT-01. A typical arrangement is shown in Fig. 3.

Communication Bus Guidelines for Maximum Number of
Devices

1. The maximum number of Comfort Zone Systems allowed on

1 device bus is 4.

2. Four Zone Controllers must be addressed 4 addresses apart,

example 4, 8, 12, 16 for a device bus with 4 Comfort Zone
Systems.

3. Home Access Module (optional) will scan a maximum of 4

Comfort Zone Systems.

4. Multiple device buses can be tied together for communication

via ISOSAT-01. An ISOSAT-02 is required for remote or
direct communications via personal computer or modem. (See
Fig. 4.)

5. Comfort Zone Systems may reside on a bus with VVT system

devices. They may receive or broadcast time to these devices
accordingly by toggling T5 enable broadcast on or off.

NOTE:

If multiple 4-zone controllers are on 1 bus, only 1 can

broadcast time. Turn all others off (T5).

Fig. 2—Daisy-Chained Comfort Zone Systems

A93251

Comfort
Zone
I/O

Comfort
Zone
I/O

Comfort
Zone
I/O

Comfort
Zone
I/O

SHIELD DRAIN WIRE

SHIELD DRAIN WIRE

NOTE 2

NOTE 1

NOTES:
  1. Use butt splices, or solder, for shield connections. Then tape up shield.

  2. Do not connect the shield drain wire at the end of Communication Bus.
     Cut and tape up to avoid shorting.

2

Summary of Contents for COMFORT ZONE ZONEKIT4ZCAR

Page 1: ...r Table 21 Wiring Diagrams 22 31 Configuration Table 32 SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause fire electrical shock or other conditions...

Page 2: ...to COM BUS a 3 wire cable must be separate from the 5 wire cable The thermostats should be located approximately 5 ft above floor and must be located within 200 ft of Comfort Zone Center SHIELDED CABL...

Page 3: ...Level back plate and tighten screws Step 4 Install Zone Dampers IMPORTANT If conditions exist for possible condensing motor must be positioned for adequate draining See Fig 6 NOTE If a multi damper en...

Page 4: ...All zone dampers and duct work must be properly supported according to local codes or SMACNA standards RECTANGULAR METAL DUCT WORK 1 Make connections using S lock and drives See Fig 10 2 Properly seal...

Page 5: ...Installation Instructions packaged with barometric bypass Failure to properly install bypass damper can cause perma nent damage to the HVAC equipment For single speed furnace applications bypass air m...

Page 6: ...ensor on room sensors Do not locate on an outside wall or next to a return air grill 1 Separate the 2 parts of sensor and mount back plate with provided flat head screw 2 Pull a 2 wire conductor throu...

Page 7: ...HEAT 1 W1 HEAT 2 W2 FAN G RV COOL 0 OR RV HEAT B Power CHR 06 Communication Bus COMFORT ZONE I O R G W R G COMM BUS CONTROLLER COMM BUS HAM R W R W R W R W R W R W OAT LAT ZT4 ZT3 ZT2 SHIELD GROUND W...

Page 8: ...TION OF A REFERENCE ZONE IN THE SYSTEM The first step in any heating or cooling cycle requires Comfort Zone to evaluate zones determine if heating or cooling is needed and select a Reference Zone The...

Page 9: ...open The factory default is 15 The only time zone dampers will exceed this position is if system fan is off or zone dampers are being calibrated 2 The Minimum Damper Position rotary position number S...

Page 10: ...4 are shown in Table 4 Under no circumstances may the W1 and Y1 contacts on the relay pack be jumpered together This is a common practice for many heat pump installations but will cause improper opera...

Page 11: ...y may vary widely For residen tial application the need for System Mode Reselect is normally not frequent unless the building has unusual architectural features or problems with HVAC system High Low T...

Page 12: ...the value of setting Press the COOL up or down setpoint buttons to change setting number and the HEAT up or down setpoint buttons to change value Refer to Table 6 for settings and their definitions 1...

Page 13: ...L up or down setpoint buttons to change toggle number and the HEAT up or down setpoint buttons to change status of toggle See Table 11 Step 12 Wiring Diagrams Refer to Tables 7 and 8 for wiring diagra...

Page 14: ...one at different times during the day and week See Fig 18 to become familiar with various parts of the 4 zone controller SYSTEM SWITCHES System switches select desired equipment operation Heat Switch...

Page 15: ...ay whenever system is in this mode Set vacation mode setpoints Setting The Clock The clock display will normally show hour minutes AM or PM and day 1 Set minutes Press SELECT MIN HR DAY button once Pr...

Page 16: ...eature can verify that each zone damper is operating properly by manually opening and closing each zone When rotary switch dial is moved onto another position Damper Service Mode will be cleared and c...

Page 17: ...omfort Zone con troller detects and replaces faulty data contained within its memory with factory selected default values Transparent Errors Occur when Comfort Zone controller de tects a system or zon...

Page 18: ...e and set points for zone 2 via the 3 wire communication bus at 1 ad dress below controller The system reads zone 2 temperature via the remote room sensor OFF T14 Smart Sensor Attached For Zone 3 The...

Page 19: ...LEDs on the CHR06 relay pack are indicating the correct relay is closed If not check for a bad relay 2 Measure voltage across common red and any de energized relay Voltage should be 24 vac 3 Apply 24...

Page 20: ...2 Configuration Error 1 Turn selection dial to position T2 T11 T12 T18 T20 T22 and T24 2 Check and correct the configuration 3 Return selection dial to any run mode position 13 Configuration Error 1 T...

Page 21: ...ed or open 1 Check wiring and sensor 2 Replace failed sensor if necessary Valid temperature range 30 180 F 47 Bus Access Error Controller can not communicate on bus 1 Check 3 wire bus between controll...

Page 22: ...296 UNIT 24 VAC R C 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFORT ZONE CENTER G W2 E...

Page 23: ...itioner Continued A94034 E UNIT 24 VAC R 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFO...

Page 24: ...ONER Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FURNACE COMFORT ZONE CENTER W2 R C C Y Y2 W W1 G NOTE Locking furnace into low...

Page 25: ...TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FURNACE COMFORT ZONE CENTER G Y2 H R1 R R1 Relay DPST Pilot Duty 24 v coil HN61KK...

Page 26: ...one Center to W2 on the furnace control board UNIT 24 VAC R C R Y1 L 2 SPEED AIR CONDITIONER 38TD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O...

Page 27: ...T ZONE SYSTEM G C R Y W2 O W2 R C L B W3 E O Y1 Y Y2 A93243 UNIT 24 VAC R C 2 SPEED HEAT PUMP 38YD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL...

Page 28: ...mp Continued UNIT 24 VAC R 2 SPEED HEAT PUMP 38YD Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y2 HEAT 1 W1 HEAT 2 W2 FAN G RV COOL O RV HEAT O OR FAN COIL COMFORT ZONE SYSTEM G C R...

Page 29: ...N position up when using Two Stage Relay Kit KGATT0101VSP Accessory Optional A93298 UNIT 24 VAC R Y W2 STANDARD SINGLE SPEED HEAT PUMP Yellow Red Blue White Brown Green Orange Black COOL 1 Y1 COOL 2 Y...

Page 30: ...OOL O RV HEAT O OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER G Y1 R1 R R1 Relay DPST Pilot Duty 24 v coil HN61KK324 or Equivalent C F W2 O W Y RELAY COIL G r e e n P5 CONNECTION AT CONTROL BOARD Blac...

Page 31: ...Configure the 4 Zone controller to act as if it were controlling a single speed heat pump Turn T 6 ON Turn T 9 T 26 OFF Set S 7 to 0 Let the 38YD perform the dual fuel optimization R W2 O W2 R G C W3...

Page 32: ...Hz Operation OFF T25 Ventilation Mode OFF T26 Two Stage Heat Pump OFF T27 Dx Sensor For LAT Checking OFF T28 Cool Without Fan OFF SETTING S 1 4 Zone Controller Bus Address 04 S 2 Max Cooling Setpoint...

Reviews: