32
English
Error
code
Item
Failure when
Consequences
Diagnostics and solutions
17 Outdoor air sensor
Value out of range
Outdoor temperature not available
18 G-Tr short circuit protection
Inverter over-current protective
circuit operates.
Short circuit voltage protection
of main circuit operates.
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check Outdoor unit board for cabling error.
20 Position Detection Circuit
Error
Position detection circuit
operates when the compressor
is operating despite removal of
3P connector.
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Replace Outdoor unit board.
21 Current Sensor Error
Current detection circuit error:
• Current value at AC side is
high when compressor is OFF
• Phase of power supply is
missing.
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check Outdoor unit board.
Check 3 phase power voltage and cables.
22
Outdoor Heat Exchange
Sensor
(TE)/(TS)
Value out of range
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check sensor, wiring and electrical connections.
23
Discharge Temperature
Sensor
(TD)
Value out of range
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check sensor, wiring and electrical connections.
24 Outdoor Fan Error
Defective detection of position
Operation of outdoor fan over-
current protection circuit
Outdoor fan locked
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check outdoor fan.
Check outdoor unit board.
26 Other Outdoor Error
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
27 Compressor Lock
Defective cabling of compressor
Compressor fault
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check 3 phase compressor power cables.
Replace compressor
28 Discharge Temperature Error Error of discharge temperature Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check for refrigerant gas leaks
Check PMV operation
Check TD sensor operation
29 Compressor Breakdown
Abnormal compressor operation Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check power supply: AC 220 V +/-10%.
Overload operation of refrigerating cycle.
Check current detection circuit at AC side.
30 Other inverter board error
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
31 High Temperature Release
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check outdoor temperature sensor TE in the
Outdoor unit.
Check Outdoor unit board.
User interface fault codes
70
Configuration
Code 104 not equal to 242 or
243 or 244
Communication is disabled
Change setting of code 104.
71
Communication of user
interface (connected to W-C-
G-Y terminal blocks)
No communication for
20 s
Code 104 = 242
No effect on user interface operation
Check wiring and connections.
72
Communication of user
interface (connected to Rc-
Rh-G2-Y2 terminal blocks)
No communication for
30 s
Code 104 = 243 or
Code 104 = 244
No effect on user interface operation
Check wiring and connections.
73 Temperature error message
Value out of range
No effect on user interface operation
Check wiring and connections.
74 Humidity error message
Value out of range
No effect on user interface operation
Check wiring and connections.
75 EEprom error message
Values in eeprom corrupted
Communication is disabled
Cycle power
Reset all parameters (see user interface
documentation).
* As this is just a warning to the user, the Alarm icon (
IMPORTANT (Unités monophasées)
Le conducteur de terre du câble de
connexion unité intérieure-unité extérieure
doit être serti à un cosse à œillet en cuivre
recuit étamé avec orifice M4 pour vis.
ATTENTION
Pour les unités triphasées, veiller à fixer le porte-
filtre et le serre-câble au câble d’alimentation
de puissance afin d’assurer la conformité aux
réglementations de sécurité et EMC. (Voir fig. 12)
) is not dispalyed and no number is associated.
Note:
- In case of diagnostic 35, in addition to the Alarm icon (
IMPORTANT (Unités monophasées)
Le conducteur de terre du câble de
connexion unité intérieure-unité extérieure
doit être serti à un cosse à œillet en cuivre
recuit étamé avec orifice M4 pour vis.
ATTENTION
Pour les unités triphasées, veiller à fixer le porte-
filtre et le serre-câble au câble d’alimentation
de puissance afin d’assurer la conformité aux
réglementations de sécurité et EMC. (Voir fig. 12)
) Domestic Water warning icon (
35
80AWX- 80AWH
English
Safety Recommendations
Refer to Safety Information Manual.
Error
code
Item
Failure when
Consequences
Diagnostics and solutions
31
High Temperature
Release
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check outdoor temperature sensor TE
��������������������
�������������������������
User interface fault codes
70
�������������
����������������������
�����������������
Communication is disabled
���������������������������
71
Communication
of user interface
(connected to
W-C-G-Y terminal
blocks)
���������������������
20 seconds
+
��������������
������������������������������������
�����������������������������
72
Communication
of user interface
(connected to
Rc-Rh-G2-Y2
terminal blocks)
���������������������
30 seconds
+
�����������������
���������������
������������������������������������
�����������������������������
73
Temperature error
message
Value out of range
������������������������������������
�����������������������������
��
Humidity error
message
Value out of range
������������������������������������
�����������������������������
75
EEprom error
message
Values in eeprom
corrupted
Communication is disabled
Cycle power
Reset all parameters (see user interface
���������������
��������������������������������������������������������
�����������������������������������������������
������
- In case of diagnostic 35, in addition to the Alarm icon (
), Domestic Water warning icon (
) will light up and Disinfection cycle icon (
������������
�����������������������������������������������������������������������
Maintenance
) will light up and Disinfection cycle icon (
35
80AWX- 80AWH
English
Safety Recommendations
Refer to Safety Information Manual.
Error
code
Item
Failure when
Consequences
Diagnostics and solutions
31
High Temperature
Release
Outdoor unit stops
Domestic water valve OFF if code 127 = 1
Check outdoor temperature sensor TE
��������������������
�������������������������
User interface fault codes
70
�������������
����������������������
�����������������
Communication is disabled
���������������������������
71
Communication
of user interface
(connected to
W-C-G-Y terminal
blocks)
���������������������
20 seconds
+
��������������
������������������������������������
�����������������������������
72
Communication
of user interface
(connected to
Rc-Rh-G2-Y2
terminal blocks)
���������������������
30 seconds
+
�����������������
���������������
������������������������������������
�����������������������������
73
Temperature error
message
Value out of range
������������������������������������
�����������������������������
��
Humidity error
message
Value out of range
������������������������������������
�����������������������������
75
EEprom error
message
Values in eeprom
corrupted
Communication is disabled
Cycle power
Reset all parameters (see user interface
���������������
��������������������������������������������������������
�����������������������������������������������
������
- In case of diagnostic 35, in addition to the Alarm icon (
), Domestic Water warning icon (
) will light up and Disinfection cycle icon (
������������
�����������������������������������������������������������������������
Maintenance
) will flash.
- Diagnostic refering to system with 2-zone kit are written in gray.
7 - SAFETY RECOMMENDATIONS
Refer to
Safety Information Manual
.