19
English
Code
Nr.
Level
Variable Name
DESCRIPTION
VALUE RANGE
DEFAULT
Min
Max
USER PARAMETERS
6
User
DAY PERIOD
User can select how many periods per day is avaialble for the scheduling.
Use Days button to select the below mentioned functions:
Day 0 - Zone 1 & 2 Schedule
0. No schedule; Schedule icon will not be displayed
1. 2 periods
2. 4 periods
3. 6 periods
Day 1 - Domestic hot water Schedule
1. 2 periods
2. 4 periods
1
3
3
2
7
User
TROOM SENSOR ADJ
ZONES
Use Days button to select below mentioned functions:
-5 °C +5 °C
0 °C
0. Room temperature sensor adjustment for zone1
1. Room temperature sensor adjustment for zone2
8
User
TEMP LIST
Depending on the selection, the following temperatures will be displayed on the user
interface:
1
8
1
1. Temperature of the zone:
Zone 1: Room temperature
Zone 2: Room temperature
Zone 3: Domestic hot water temperature
2. LWT
3. Domestic hot water temperature
4. TWB
5. TW1 (Water temperature in Zone 1)
6. TW2 (Water temperature in Zone 2)
7. Not used
8. Not used
9
User
FAULT CODES
Hydronic module, zone kit, user interface and outdoor unit fault codes and alarms are
scrolled for one second.
-
-
-
10
User
FAULT HISTORY
Stores the recent 4 fault codes and alarms.
-
-
-
INSTALLER PARAMETERS
System setup
100
Inst.
SYSTEM TYPE
This parameter is used by the Installer to determine the System type:
1
2
1
Select 1 if there is no zone kit connected, otherwise select 2.
101
Inst.
NOT USED
102
Inst.
NOT USED
103
Inst.
GMC ADDRESS
This parameter is used to identify if the board is acting as hydronic module board (master)
or zone kit board (slave).
1
2
1
To modify this parameter, connect the user interface to the specific board through J5
connector; the user interface wiring must be as per the connection to W-C-G-Y terminal
blocks (see user interface manual).
1. Master
2. Slave
104
Inst.
NUI ADDRESS
Specifies the user interface connection. If this parameter is not set properly, the user
interface does not work.
242
244
242
242. User interface connected on W-C-G-Y, see user interface manual
243. User interface connected on Rc-Rh-G2-Y2 (see user interface manual) and placed in
zone 1
244. User interface connected on Rc-Rh-G2-Y2 (see user interface manual) and placed in
zone 2
105
Inst.
ZONES CTRL
This parameter defines the controls in zones. Use Days button to select:
0
4
0
0. Zone 1 CTRL
0. No control
1. User interface (additional user interface, connected on Rc-Rh-G2-Y2)
2. Sensor
3. Thermostat
4. Unit user interface removed from the unit and installed in the zone; connection on
W-C-G-Y
1. Zone 2 CTRL
0. No control
1. User interface (additional user interface, connected on Rc-Rh-G2-Y2)
2. Sensor
3. Thermostat
4. Unit user interface removed from unit and installed in the
zone; connection on W-C-G-Y