CL-3
UNIT START-UP:
ELECTRICAL
UNIT SUPPLY VOLTAGE
L1-L2 _____________
L2-L3 ________________
L3-L1 ________________
COMPRESSOR 1 AMPS
C1-L2 _____________
C1-L2 ________________
C1-L3 ________________
COMPRESSOR 2 AMPS
C2-L1 _____________
C2-L2 ________________
C2-L3 ________________
SUPPLY FAN AMPS
CV________________
VAV*_________________
EXHAUST FAN AMPS
CV________________
VAV*_________________
ECW MOTOR AMPS
___________________
_____________________
*VAV fan readings must be taken with a true RMS meter for accurate readings.
TEMPERATURES
COOLING OAT
______________ °F DB
_______________°F WB
COOLING LAT
______________ °F DB
_______________°F WB
HEATING OAT
______________ °F DB
HEATING LAT
______________ °F DB
REFRIGERATION SYSTEM
Note: All 62X units are equipped with lead circuit digital compressors and hot gas reheat (HGRH). Additionally, some 62X units
are equipped with a liquid subcooling reheat on all circuits and lag circuit digital compressor. When checking refrigeration system
performance, HGRH must be disabled, digital compressors must be manually forced to 100% operation, and the liquid subcooling
circuit(s) must be active.
SUCTION LINE TEMPERATURE
CIRCUIT NO. 1___________ ° F
CIRCUIT NO. 2 ____________ ° F
SUCTION PRESSURE
CIRCUIT NO. 1___________ IN. WG
CIRCUIT NO. 2 ____________ IN. WG
SUPERHEAT
CIRCUIT NO. 1___________ ° F
CIRCUIT NO. 2 ____________ ° F
LIQUID TEMPERATURE
CIRCUIT NO. 1___________ ° F
CIRCUIT NO. 2_____________ ° F
LIQUID PRESSURE
CIRCUIT NO. 1___________ IN. WG
CIRCUIT NO. 2 ____________ IN. WG
SUBCOOLING
CIRCUIT NO. 1___________ ° F
CIRCUIT NO. 2 ____________ ° F
Note: All 62X units are charged at factory environmental conditions. Refrigerant charge may need to be adjusted based on local en-
vironmental and application conditions. Adjust charge as needed to achieve 10-12°F of subcooling with HGRH disabled, all com-
pressors operating at 100%, and all subcooling circuits active (if equipped).
HEATING
HEATING SOURCE
______________
INLET PRESSURE
______________ IN. WG
MANIFOLD PRESSURE
LOW
______________ IN. WG
HIGH _______________ IN. WG
CO
2
IN FLUE GAS
LOW
______________ %
HIGH _______________ %
CO IN FLUE GAS
LOW
______________ PPM
HIGH _______________ PPM
DRAFT FAN PRESSURE
LOW
______________ IN. WG
HIGH _______________ IN. WG
ELECTRIC HEATER AMPS
______________ AMPS
HOT WATER ENTERING TEMPERATURE______________ ° F
HOT WATER LEAVING TEMPERATURE ______________ ° F
HOT WATER FLOW RATE
______________ GPM
COMPRESSOR OIL LEVEL
FILL IN THE CIRCLE TO INDICATE SIGHT GLASS OIL LEVEL.
CIRCUIT 1
CIRCUIT 2