37
Fig. 14 — Installation Wiring Diagram (cont)
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
FIELD POWER SUPPLY 208/230/460/575-3-60. MINIMUM CIRCUIT AMPACITY AND
MAXIMUM SIZE AND TYPE OF BRANCH-CIRCUIT SHORT-CIRCUIT AND GROUND-FAULT
PROTECTION PER UNIT RATING PLATE. PROVIDE DISCONNECTING MEANS AS REQUIRED.
TYPICAL MOTORS AND COMPRESSORS SHOWN. SEE CONNECTION DIAGRAM ON MOTOR
OR COMPRESSOR FOR ACTUAL WIRING DETAIL.
IF POWER MONITOR OUTPUT CONTACTS DO NOT TRANSFER WHEN POWER IS APPLIED TO
UNIT (LED GLOWS RED DURING FAULT CONDITIONS):
1. VERIFY THAT ALL THREE PHASES ARE PRESENT AND ARE OF THE CORRECT VOLTAGE. IF
ALL THREE PHASES ARE PRESENT AND ARE OF THE CORRECT VOLTAGE, PHASE ROTATION
MAY BE INCORRECT. PERFORM STEP 2.
2. DISCONNECT POWER TO THE UNIT. VERIFY THAT POWER IS IN FACT DISCONNECTED.
SWAP ANY TWO OF THE THREE UNIT POWER SUPPLY WIRES. WHEN POWER IS REAPPLIED,
OUTPUT CONTACTS SHOULD NOW TRANSFER.
HP
208/230 VOLT
460 VOLT
1/2 THRU 3
14 AWG
14 AWG
5
12 AWG
14 AWG
7-1/2
10 AWG
14 AWG
10
8 AWG
12 AWG
15
6 AWG
12 AWG
20
4 AWG
10 AWG
# : BLOWER MOTOR MINIMUM WIRE SIZE
FUSE NO.
CLASS
VAC
AMPS-208/230V
AMPS-460V
XFMR
TIME DELAY
CC
600
3
2
350VA
YES
CC
600
2
1.5
250VA
YES
CC
600
2
1.5
200VA
YES
CC
600
1.5
3/4
150VA
YES
F2, F9, F10
CC
600
1
1
N/A
YES
CC
600
16
16
350VA
YES
CC
600
10
10
250VA
YES
CC
600
10
10
200VA
YES
CC
600
6
6
150VA
YES
CB
FUSE TABLE
F1, F3
INSTALL THE LIQUID LINE SOLENOID VALVE (LLS) and BLEED OFF SOLENOID (BOS) IN AIR
HANDLING UNIT (AHU) FOR FIELD WIRING.
2
1
6
8
ABBREVIATION
COLOR
BK
BLACK
BL
BLUE
BR
BROWN
G
GREEN
O
ORANGE
PK
PINK
PR
PURPLE
R
RED
W
WHITE
Y
YELLOW
WIRE COLOR LEGEND
NOTE: NUMBER PLACED AFTER DASH
FOLLOWING COLOR CODE INDICATES WIRE
GAGE. EX. - BK-12 IS A BLACK, 12 AWG WIRE.
NO NUMBER AFTER COLOR CODE INDICATES 18
AWG WIRE. EX. - BK IS A BLACK 18 AWG WIRE.
Wire Size
Maxium Run
18 AWG
50 Feet
16 AWG
75 Feet
14 AWG
100/125 Feet
14 AWG
150/200 Feet
24 Volt Class 2 Minimum Wire Size
MODEL
208/230 VOLT
460 VOLT
575 VOLT
03
12 AWG
12 AWG
12 AWG
04
12 AWG
12 AWG
12 AWG
05
12 AWG
12 AWG
12 AWG
06
12 AWG
12 AWG
12 AWG
07
10 AWG
12 AWG
12 AWG
08
10 AWG
12 AWG
12 AWG
## : COMPRESSOR MINIMUM WIRE SIZE
ITEM
FUNCTIONAL
DESIGNATION
LINE NUMBER
DESCRIPTION
101
SFR
148
Supply Fan Motor Relay
102
MSP-SF
38
Motor Starter Protecon-Supply Fan
103
SF-VFD
38
Supply Fan-Variable Frequency Drive
104
CC1
110
Compressor Contactor no. 1
105
CC1-A1, CC1-A2
#
"CC1" Auxiliary Contact no. 1 and 2
107
MSP-CC1
1
Motor Starter Protecon-“CC1”
115
EFR
152
Exhaust Fan Relay
116
MSP-EF
46
Motor Starter Protecon-Exhaust Fan
118
EGB
4
Equipment Grounding Bar
119
F1, F2, F3
59, 60, 61
Fusing-See Fuse Table on this sheet
120
CB
71
Circuit Breaker-See Fuse Table on this sheet
122
MSP-OF1
22
Motor Starter Protecon-Outdoor Fan no. 1
126
OF1VFD
22, 25
Outdoor Fan Variable Frequency Drive no. 1
130
MRC1
202
Modulang Reheat Controller no. 1
131
PDB
1, 2, 3
Power Distribuon Block
132
PM
59, 71
Power/Phase Monitor
133
RHR
156
Reheat Relay
135
T1
62, 67
Control Transformer no. 1
136
T2
200
Control Transformer no. 2
137
TB1
Sheet 2-5
Terminal Board no. 1
138
TB2
71
Terminal Board no. 2
139
TB3
204, 216
Terminal Board no. 3
140
TB-A
Sheet 5
Terminal Board no. -A
147
MSP-WM
54
Motor Starter Protecon-Wheel Motor
148
WMVFD
54
Wheel Motor Variable Frequency Drive
150
WM-CS
55, 329
Wheel Motor Current Sensor
LEGEND - ITEMS INSIDE CONTROL PANEL
# SEE LINE NUMBER TO THE RIGHT OF CONTACTOR COIL ON WIRING DIAGRAM.
ITEM
FUNCTIONAL
DESIGNATION
LINE NUMBER
DESCRIPTION
101
BCTL
165
BCTL
102
BOS1
132
Bleed-Off Solenoid no. 1
103
CCH1
4
Compressor Crankcase Heater No. 1
104
CM1
2
Compressor Motor No. 1
105
DPT260
340, 342
Differenal Pressure Transmier 260 (SF and EF)
106
EFM1
47
Exhaust Fan Motor No. 1
107
FS
71
Fire Stat
108
HP1
110
High Pressure Switch No. 1
109
LP1
265
Low Pressure Switch No. 1
110
OFM1
29
Outdoor Fan Motor No. 1
111
SFM1
39
Supply Fan Motor No. 1
112
WM
55
EC Wheel Motor
LEGEND - ITEMS OUTSIDE CONTROL PANEL
# SEE LINE NUMBER TO THE RIGHT OF CONTACTOR COIL ON WIRING DIAGRAM.
FACTORY Y
L
L
A
M
R
O
N
G
N
I
R
I
W
OPEN CONTACTS
FIELD D
E
S
O
L
C
Y
L
L
A
M
R
O
N
G
N
I
R
I
W
CONTACTS
EARTH E
L
B
A
I
F
I
T
N
E
D
I
D
N
U
O
R
G
TERMINAL
CHASSIS (PANEL) GROUND
COIL
SYMBOL LEGEND
NON-IDENTIFIABLE TERMINAL,
OTHER WIRE JUNCTIONS,
INCLUDING SCHEMATIC