WIRING DIAGRAM #0962I-5322 | 62XJ04PBJT-JFATACW | 208/230/460/575-3-60 | SHEET 5 OF 8 | 10/31/2017 DWN
LWF
CHK
DS
.
G
W
ZAT
ZS Room
Sensor
Green
Gn
d
RNET+
RNET-
+12V
Gn
d
Rn
et
+
Rn
et
-
+12V
Se
nse
EQUIPMENT
TOUCH
Gn
d
Rn
et
+
Rn
et
-
+24
V
AC
Red
Black
White
FIELD INSTALL
4
K3
K4
-12V
Rnet
+
Rnet
-
+12V
TB4
TB5
4
BK
R
Equipment Touch
Connector
(Blue)
ECA-T/RH
Install
OAT
under the OA
hood, sensing the ambient
temp.
Off On
Auto
Universal Input
Mode Select
Aux Power Out
Power
Off
On
Port 1
Rnet
Gnd
RNET+
RNET-
+12V
UO-8
UO-7
UO-6
UO-5
Gnd 8
UO-4
+ 7
Gnd 6
UO-3
+ 5
Gnd 4
UO-2
+ 3
Gnd 2
UO-1
+ 1
Gnd 8
+ 7
Gnd 6
+ 5
Gnd 4
+ 3
Gnd 2
+ 1
UI-8
UI-7
UI-6
UI-5
8 Gnd
UI-4
7 +
6 Gnd
UI-3
5 +
4 Gnd
UI-2
3 +
2 Gnd
UI-1
1 +
UI-12
UI-11
UI-10
UI-9
Rnet Local
Access
Gnd
Rnet+
Rnet-
+12V
Sense
8 Gnd
7 +
6 Gnd
5 +
4 Gnd
3 +
2 Gnd
1 +
8 Gnd
7 +
6 Gnd
5 +
4 Gnd
3 +
2 Gnd
1 +
Gnd
24VAC
0
5
0
5
1
2
3
4
5
6
7
8
10's
1's
Module
Address
NET +
NET -
Shield
Port 1 BT485
Port 2a BT485
485
Port 1
ARC-
156
2 Wire
EIA-
485
4 Wire
EIA-
232
Port 2a
XNET +
XNET -
Gnd
Port 2a
NET +
NET -
n/c
n/c
Signal Ground
Tx +
Tx -
Rx +
Rx -
Tx
Rx
DTR
DCD
2 wire 4 wire EIA-232
mA
Thermistor/
Dry Contact/
RTD
Volts
Off
2
1
Assigned
Default
On
Off
BAS Port
IP Addr
Enhanced
Access Port 2a
BA
Cne
t
BAS Port Sengs
BAUD
4
5
Protocols
6
7
8
9600
Off
Off
MSTP (m)
Off
Off
Off
19.2K
Off
On
MSTP (s)
On
Off
Off
38.4K
On
Off
PTP
Off
On
Off
76.8K
On
On
N2
On
On
Off
Modbus
Off
Off
On
Lon SLTA
On
Off
On
Lon Opon
Off
On
On
Fuse
24VDC
200mA maximum
100
LAN
LINK
10/100 BaseT
Ethernet Port E1
Xnet
Expansion
See BAS Table Below
+ 3V
Gnd
External
Baery
Ext. Ba.
Int. Ba.
0-10Vdc
0-20 mA
Relay
Pot
UO-1
UO-2
UO-3
UO-4
UO-5
UO-6
UO-7
UO-8
Set Pot Full CW
Port 2b
Format
I/O PRO 812u
CONTROLLER
SEE TB4 ON UNIT
WIRING DIAGRAM
R
TB4
BL
FOR FIELD:
BACNET
CONNECTION
FACTORY WIRING
FIELD WIRING
TERMINAL BOARD
SYMBOL LEGEND
USE 18 AWG WIRE MINIMUM. TO MINIMIZE
INTERFERENCE PROBLEMS:
USE SHIELDED WIRE ON ALL ANALOG INPUTS
AND OUPUTS. DO NOT RUN 0-10 VOLT DC
SIGNAL WIRING IN THE SAME CONDUIT AS
LINE VOLTAGE WIRING OR WITH WIRING
THAT SWITCHES HIGHLY INDUCTIVE LOADS
SUCH AS CONTACTOR AND RELAY COILS.
GROUND ONE END OF THE DRAIN (SHIELD)
WIRE.
WHEN 0-10 VOLT DC SIGNAL WIRING MUST
CROSS CLOSE TO CABLE OR NONMETALLIC
CONDUIT CONTAINING LINE VOLTAGE
WIRING OR WIRING THAT SWITCHES HIGHLY
INDUCTIVE LOADS, IT MUST CROSS
PERPENDICULAR (90 DEGREES) TO IT.
KEEP THE 0-10 VOLT DC SIGNAL WIRING AS
SHORT AS POSSIBLE.
LON
1
2
Port 2b
ECHELO
N
LonWorks Card (oponal)
FOR FIELD: BAS OR EMS
CONNECTION
3V Lium Baery
CR-123A
-
+
Error Codes:
Chase = OK
0 = Download Required
1 = Control Program Error
2 = RAM full
3 = Comm set-up error
4 = System error
8 = Formang
Blinking Dot = ‘Run’
8.
DO NOT APPLY 24V AC
TO UNIVERSAL OUTPUTS
External 24VDC relay coil only
24V AC
R
TB-A
GND
GND
24VDC
USE SHIELDED WIRE FOR ALL
ANOLOG INPUTS
WIRE ALL SHIELD WIRES TO CLOSEST TB-A or TB-D
“GND” TERMINAL AT THE CONTROL PANEL
4
24VDC
4
BK
W
W
BK
Rosenburg EC
motor, 0-10vdc
SFM
0-10
vdc
GND
4
5
4
W
BK
BK
W
EFM
0-10
vdc
GND
4
5
Rosenburg EC
Motor, 0-10vdc
4
4
BK
W
W
BK
BK
W
W
BK
-
+
WMVFD
AI1
DI-C
7
2
4
BK
W
W
BK
Wheel Motor
VFD, 0-10vdc
Heat Modulang
See Elec. Heater
or Gas Furnace
for exact wiring
connecons
4
2
temp
sensor
V
ou
t
com
V
in
pw
r
BK
G
DxLAT1
BK
W
DxLAT1: INSTALL AFTER DX COIL
#1 UPSTREAM OF REHEAT COIL
SA-T/RH
Field install
and wire
1
temp
sensor
V
ou
t
com
V in
pw
r
4
Note: THE SUPPLY/DISCHARGE AIR TEMPERATURE/RELITIVE HUMIDITY
(SA-T/RH) IS FACTORY SUPPLIED FOR FIELD INSTALLATION IN SUPPLY AIR
DUCT. SENSOR MUST BE INSTALLED DOWNSTREAM OF HEATER WHERE
IT CANNOT “SEE” ANY HEATING ELEMENTS AND WHERE SUFFICIENT
MIXING OF DISCHARGE AIR OCCURS. USE 18 AWG SHIELDED WIRE. DO
NOT RUN SENSOR WIRING IN THE SAME CONDUIT AS LINE VOLTAGE
WIRING OR WITH WIRING THAT SWITCHES HIGHLY INDUCTIVE LOADS
SUCH AS CONTACTOR AND RELAY COILS.
1
W
4
2
4
OAT
BK
W
4
RAT
BK
W
RAT: INSTALL SENSING THE RETURN
AIR UPSTREAM OF ECW
4
WExAT
BK
W
WExAT: INSTALL SENSING THE
EXHAUST AIR DOWNSTREAM OF ECW
SENSORS
DESCRIPTION
CFI
Clogged Filter Indicator
DPT-260
Differenal Pressure Transmier
SAT
Supply Air Temperature Sensor
OA-T/RH
Outdoor Air Temp/Relave Humidity Sensor
SA-RH
Supply Air Relave Humidity
ZS
Zone Temperature Sensor - Standard
CC1-CS, CC2-CS
Compressor #1 & #2 Current Sensor
DxLAT
Dx Leaving Air Temperature Sensor
WM-CS
Wheel Motor Current Sensor
SF-APS, EF-APS
Supply Fan / Exhaust Fan Air Press. Switch
WFR
Water Flow Relay
LP1, LP2
Low Pressure Switch, Ckt. #1 & #2
SD
Smoke Detector
K3
K4
5
9
Unloader Relay #1
R
PR
Unloader #1
U1
R
TB1
GY
PR
14
13
2
WARNING!!!
DO NOT leave dip
switch #1 “ON.”
This will result in loss
of Equipment Touch
and Network
Communicaons.
Install
ECA-T/RH
aer the
ECW, sensing the modified
temp/humidity.
3
3
MRC
+S
-S
Modulang
Reheat, 0-10vdc
ALL FIELD INSTALLED SENSORS SHOULD BE WIRED TO THE
CONTROLLER FOR FACTORY TESTING WITH TEMPORARY
WIRING AND LEFT IN THE UNIT AFTER TEST. TEMPORARY
WIRING SHOULD BE REMOVED FOR PERMANENT
INSTALLATION DURING UNIT INSTALLATION. LABEL
SENSORS PER THE WIRING DIAGRAM.
To wall mount the
Equipment Touch, remove
the factory installed cable
and wire +24VAC to TB4 “K3”
and wire Gnd to TB4 “K4”. If
there is a ZS sensor installed,
wire Rnet+ and Rnet- to the
ZS sensor Rnet+ and Rnet-
terminals. Otherwise, wire to
TB5 Rnet+ and Rnet-