17
Table 1 — Physical Data — 62X A Cabinet (cont)
LEGEND
* Optional.
NOTE: For unit and component weights, refer to the latest edition of
Carrier's Dedicated Outdoor Air Systems Builder.
UNIT 62X A CABINET
03
04
05
06
07
08
NOMINAL CAPACITY (TONS)
3
4
5
6
7
8
OUTDOOR AIR FILTERS
Quantity … Size (in.) with ERV
Standard 2-in. MERV 8
2...24x24
Use B Cabinet
Optional 4-in.
MERV 8
2...24x24
MERV 11
2...24x24
Use B Cabinet
MERV 14
2...24x24
Quantity … Size (in.) without ERV
Standard 2-in. MERV 8
1..20x24
1...16x20, 1...20x20
Optional 4-in.
MERV 8
1...20x24
1...16x20, 1...20x20
MERV 11
1...20x24
1...16x20, 1...20x20
MERV 14
1...20x24
1...16x20, 1...20x20
OPTIONAL ERV
Type
Molecular Sieve
Use B Cabinet
Diameter ... depth (in.)
24...4, 32...4, 36...4
Use B Cabinet
OPTIONAL ERV FILTERS
Quantity … Size (in.)
with 24 in. ERV
4...12x24
4...12x24
4...12x24
Use B Cabinet
with 32 in. ERV
6...18x20
6...18x20
6...18x20
Use B Cabinet
with 36 in. ERV
2...20x20,
2...20x24
2...20x20,
2...20x24
2...20x20,
2...20x24
Use B Cabinet
Use B Cabinet
OPTIONAL EXHAUST FAN
Backward Curved ECM (mm)
280, 355
Airfoil (in.)
—
Backward Inclined (in.)
—
Nominal Cfm
450
600
750
900
1050
1200
ECM
—
Electronically Commutated Motor
ERV
—
Energy Recovery Ventilator
FPI
—
Fins per Inch
LP
—
Liquid Propane
OA
—
Outdoor Air
SCR
—
Silicon-Controlled Rectifier